Installation dimensions
12"
(30.5 cm)
2" (50.1 mm)
Venting methods
This canopy hood is factory set for venting through the roof or wall.
min.
An 8" (20.3 cm) round vent system is needed for installation (not included). The hood exhaust opening is 8" (20.3 cm) round.
Vent system can terminate either through the roof or wall. To vent through a wall, a 90° elbow is needed.
Rear discharge
| 12" |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| vent and power | ||||
|
| (30.5 cm) |
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
| supply cable entry | ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| location | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 21" |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| (53.3 cm) |
|
|
|
| |||||
side |
|
|
|
|
|
|
|
|
|
|
| min. |
|
| side | |||||
cabinet |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| cabinet | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 36" (91.4 cm) |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
A 90° elbow may be installed immediately above the hood.
For non-vented (recirculating) installations
Should it not be possible to vent cooking fumes and vapors to the outside, the hood can be used in the
roof cap
| minimum |
|
|
|
| ||
|
|
|
|
|
| ||
|
|
|
| 30" (76.2 cm) min. |
|
| |
|
|
|
| bottom of canopy to |
|
| |
|
| centerline |
|
|
| ||
|
|
| cooking surface |
|
| ||
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Venting Requirements
Vent system must terminate to the outside.
Do not terminate the vent system in an attic or other enclosed area.
8" (20.3 cm) round vent
8" |
|
(20.3 cm) |
|
round vent | wall |
| cap |
deflector |
8"
(20.3 cm)
round vent
Do not use 4" (10.2 cm)
Use metal vent only. Rigid metal vent is recommended. Do not use plastic or metal foil vent.
For the most efficient and quiet operation:
■Use a straight run or as few elbows as possible.
■Use no more than three 90° elbows.
■Make sure there is a minimum of 24" (61 cm) of straight vent between the elbows if more than one elbow is used.
■Do not install two elbows together.
■Use duct tape to seal all joints in the vent system.
■Use caulking to seal exterior wall or roof opening around the cap.
Cold weather installations
An additional backdraft damper should be installed to minimize backward cold air flow and a nonmetallic thermal break to minimize conduction of outside temperatures as part of the vent system. The damper should be on the cold air side of the thermal break.
The break should be as close as possible to where the vent system enters the heated portion of the house.
Make-up air
Local building codes may require the use of
Consult your HVAC professional for specific requirements in your area.
Roof venting | Wall venting | |
|
| (recirculating) |
Calculating Vent System Length
To calculate the length of the system you need, add the equivalent feet (meters) for each vent piece used in the system.
Vent piece | 8" (20.3 cm) round |
45° elbow | 2.5 feet |
| (0.8 m) |
90° elbow | 5.0 feet |
| (1.5 m) |
Maximum equivalent vent length is 50 feet (15.2 meters).
90° elbow |
| 6 ft. (1.8 m) |
| wall cap |
|
|
|
|
|
|
|
|
|
| Example vent | ||
|
|
|
|
|
|
|
| system | |
|
|
|
| 1 | — 90° elbow | = | 5 ft. | (1.5 m) | |
|
| ||||||||
|
|
| |||||||
2 | ft. |
| |||||||
(0.6 m) |
| 8 ft. (2.4 m) straight | = | 8 ft. | (2.4 m) | ||||
|
|
|
| ||||||
|
|
| 1 | — wall cap | = | 0 ft. | (0 m) | ||
|
|
| |||||||
|
|
|
|
|
|
|
|
| |
|
|
|
| system length | = | 13 ft. | (3.9 m) |