TROUBLESHOOTING

Reset Operation

If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation, reset the thermostat

by pressing the , and TIME buttons simultaneously.

If the thermostat has power, has been reset and still does not function correctly contact your heating/cooling service person or place of purchase.

Symptom

Possible Cause

Corrective Action

 

 

 

No Heat/No Cool/No Fan

1. Blown fuse or tripped circuit breaker.

Replace fuse or reset breaker.

(common problems)

2. Furnace power switch to OFF.

Turn switch to ON.

 

3. Furnace blower compartment door or

Replace door panel in proper position to engage safety

 

panel loose or not properly installed.

interlock or door switch.

 

 

 

No Heat

1. System Switch not set to Heat.

Set System Switch to Heat and raise setpoint above

 

 

room temperature.

 

2. Loose connection to thermostat or

Verify thermostat and system wires are securely attached.

 

system

Diagnostic: Set System Switch to Heat and raise the

 

3. Heating System requires service or

setpoint above room temperature. Within a five minutes

 

thermostat requires replacement.

the thermostat should make a soft slick sound. This

 

 

sound usually indicates the thermostat is operating

 

 

properly. If the thermostat does not click, try the reset

 

 

operation listed above. If the thermostat does not click

 

 

after being reset contact your heating and cooling

 

 

service person or place of purchase for a replacement.

 

 

If the thermostat clicks, contact the furnace manufac-

 

 

turer or a service person to verify the heating system is

 

 

operating correctly.

 

 

 

No Cool

1. System Switch not set to Cool.

Set System Switch to Cool and lower setpoint below

 

 

room temperature.

 

2. Loose connection to thermostat or

Verify thermostat and system wires are securely attached.

 

system.

Same procedures as diagnostic for No Heat condi-

 

3. Cooling System requires service or

tion except set the thermostat to Cool and lower the

 

thermostat requires replacement

setpoint below the room temperature. There may be up

 

 

to a five minute delay before the thermostat clicks in

 

 

Cooling if the compressor lock-out option is selected in

 

 

the configuration menu (Item 6).

 

 

 

Heat, Cool or Fan Runs

1. Possible short in wiring.

Check each wire connection to verify they are not

Constantly

2. Possible short in thermostat.

shorted or touching together. No bare wire should

 

3. Possible short in Heat/Cool/Fan

stick out from under terminal screws. Try resetting the

 

system.

thermostat as described below. If the condition persists,

 

4. Fan Switch set to Fan On.

the manufacturer of your system or service person

 

 

can instruct you on how to test the Heat/Cool/ system

 

 

for correct operation. If the system operates correctly,

 

 

replace the thermostat.

 

 

 

Furnace CyclesToo Fast orToo Slow

1. The location of the thermostat and/

Item 4 (CR Heat) or 5 (CR Cool) in the Configuration

Cooling CyclesToo Fast orToo Slow

or the size of the Heating or Cooling

Menu is the adjustment that controls the cycle rate. If

(narrow or wide temperature swing)

System may be influencing the

an acceptable cycle rate is not achieved using the FA

 

cycle rate.

(Fast) or SL (Slow) adjustment contact a local service

 

 

person for additional suggestions.

 

 

 

Thermostat Setting and

1. Thermostat thermometer setting

The thermometer can be adjusted +/- degrees as listed

Thermometer Disagree

requires adjustment.

in item 8 of the Configuration Menu. No other adjust-

 

 

ment is possible.

 

 

 

Clock Loses or Gains Time

1. Loss of power to thermostat.

The thermostat will maintain its program in memory

 

 

even with no power but the clock time will be incorrect

 

 

when power is restored. See No Heat/No Cool /No Fan

 

 

(common problems) above for items to check in the

 

 

system.

 

 

 

Heat or Cool Starts Early

1. EMR activated.

See Configuration Menu (Item 3)

 

 

 

Thermostat Does Not Follow

1. AM or PM set incorrectly in program.

Check current clock and program settings including

Program

2. AM or PM set incorrectly on the clock.

the AM or PM designations for each time period. If a

 

3. Voltage spike or static discharge.

voltage spike or static discharge occurs use the Reset

 

4. See “Heat or Cool Starts Early” above.

Operation listed above.

 

 

 

Blank Display and/or Keypad Not

1. Voltage Spike or Static Discharge.

If a voltage spike or static discharge occurs use the

Responding

 

Reset Operation listed above.

 

 

 

9

Page 9
Image 9
White Rodgers 1F80-0261 specifications Troubleshooting, Reset Operation

1F80-0261 specifications

The White Rodgers 1F80-0261 is a programmable thermostat known for its user-friendly interface and advanced features that cater to modern heating and cooling needs. With its sleek design and intuitive controls, it offers a seamless blend of functionality and aesthetics, making it an attractive choice for homeowners looking to optimize their HVAC systems.

One of the standout features of the 1F80-0261 is its 7-day programming capability. This allows users to create specific heating and cooling schedules for each day of the week, accommodating varying routines and preferences. Each day can have different settings for morning, daytime, evening, and night periods, promoting energy efficiency and comfort. The thermostat also has a vacation hold feature that allows homeowners to program a temporary setting while they are away, preventing unnecessary energy consumption.

The 1F80-0261 utilizes advanced technologies to enhance its performance. The thermostat employs a precise temperature control mechanism that ensures consistent and accurate heating and cooling. Additionally, it features an energy-saving mode that helps reduce energy bills by optimizing system performance without sacrificing comfort. This mode is particularly beneficial during peak energy usage hours.

The thermostat's large, easy-to-read display improves usability, allowing users to view current temperatures and settings at a glance. Backlighting ensures visibility even in low-light conditions, further enhancing user experience. The graphical interface is designed to guide users through programming options, making it accessible for individuals of all technical skill levels.

Another notable characteristic is the compatibility of the 1F80-0261 with a wide range of heating and cooling systems, including conventional heating systems and heat pumps. This versatility enables users to integrate the thermostat into their existing infrastructure seamlessly.

Additionally, the 1F80-0261 offers filter change reminders that alert users when it's time to replace or clean their system’s filters. This feature helps maintain air quality and system efficiency by ensuring that filters are regularly attended to.

In summary, the White Rodgers 1F80-0261 is a programmable thermostat that combines advanced programming features, user-friendly design, and energy-efficient technology. Its ability to cater to diverse HVAC systems, alongside its focus on improving comfort and reducing energy costs, makes it a noteworthy option for any homeowner seeking control over their indoor climate.