!CAUTION
A cooling anticipation setting of less than 10 may cause decreased compres- sor life.
SET
To adjust heat anticipation, press CLOCK
and DAYSET at the same time. The display will
show HEAT 5 (this is the factory prepro- grammed heating anticipation setting). You may select any anticipation setting from 2 to 40 (note that for hydronic systems, a minimum anticipation setting of 15 is recommended). Whenever adjusting an- ticipation, increase or decrease the dis- played number by only one or two digits, then let the system run for a while to see if the adjustment is sufficient. If the heat
cycles are too short, press TIMEFWD to increase the cycle time. If the heat cycles are too long,
press | BACKTIME to decrease the cycle time. To | ||
set cooling anticipation, press | SET | and | |
CLOCK | |||
DAYSET | at the same time again. The display will |
show COOL 14 (factorypreprogrammedcool-
ing anticipation). Use the | TIME | and | TIME | |
FWD | BACK | |||
buttons to adjust anticipation. Press | PRGMRUN to |
return to your program.
•LOW BATTERY INDICATOR — The word BATTERY will flash on the display if the "AA" alkaline batteries are low and should be replaced. The word BATTERY will be displayed continuously