INSTALLER/CONFIGURATION MENU
To enter the Configuration Menu, SYSTEM must be set to HEAT, COOL, Em or AUTO. Press the Menu button for at least 5
seconds. The display will show item #1 in the table below. Press Menu button to advance to the next menu item. Press or to change an item option.
INSTALLER/CONFIGURATION MENU
SCREENMENU | MS2/ | HP1/ | DISPLAYED | Press | or | to | COMMENTS |
NUMBER | SS1 | HP2 | (FACTORY DEFAULT) | select from listed options |
| ||
|
|
|
|
|
|
| |
01 | | | (OFF) Lk |
| L |
| Selects Keypad Lockout. |
|
|
|
|
|
|
| (Not available on earlier models) |
02 | | | (000) Lk | 001 | to 999 |
| Selects Keypad lockout combination number |
03 | | | (MS 2) | SS1, HP1, HP2 |
| Selects | |
|
|
|
|
|
|
| Heat Pump 1 (HP 1, 1 compressor), |
|
|
|
|
|
|
| or Single Stage (SS 1), Heat Pump 2 (HP 2, 2 |
|
|
|
|
|
|
| compressor or 2 speed compressor) |
04 | |
| (GAS) | ELE |
| Select Gas or Electric heat | |
|
| | (ELE) | GAS |
|
| |
05 | | | (0) CS | 1, 2, 3, 4, 5, 6 |
| Selects Cool Savings | |
|
|
|
|
|
|
| Value 1 (low) to 6 (high), Value 0 Disables Feature |
06 | | | (On) E | OFF |
| Selects Energy Management Recovery (EMR) | |
|
|
|
|
|
|
| On or OFF. |
07 |
| | (ME) | SL, FA |
| Adjustable Anticipation: | |
|
|
| CR Heat |
|
|
| Selects heating cycle rate for MS or SS |
08 |
| | (ME) | SL, FA |
| Adjustable Anticipation: Selects the cycle | |
|
|
| CR Cool |
|
|
| rate for cooling (only when MS2 or SS1 |
|
|
|
|
|
|
| is selected in item 1) |
09 | | | (ME) | SL, FA |
| Adjustable Anticipation (Heat Pump) | |
|
|
| CR Heat Pump |
|
|
| (only when heat pump is selected in #1) |
10 | | | (FA) |
| SL |
| Selects the cycle rate for Emergency |
|
|
| CR Em |
|
|
| mode and Auxiliary stage if Heat Pump is |
|
|
|
|
|
|
| selected in item 1) |
11 | | | (OFF) CL | CL On |
| Compressor Lockout Time | |
12 | | | Select System Switch Configuration with automatic | ||||
|
|
|
| changeover capability | |||
|
|
|
|
| |||
13 | | | (On) dL | dL OFF |
| Selects Display Light On or OFF | |
14 | | | 0 | 1 HI, 2 HI, 3 HI, 4 HI, | Adjustable Ambient Temperature Display | ||
|
|
| (current temperature) | 1 LO, 2 LO, 3 LO, 4 LO |
| ||
15 | | | °F |
| °C |
| Selects Fahrenheit/Celsius Temperature Display |
16 | | | L (90) Heat | L 62 to L 89 |
| Selects Limited HEAT Range | |
17 | | | L (45) Cool | L 46 to L 82 |
| Selects Limited COOL Range | |
18 | | | P7 |
| P3 |
| Defaults for 7 day programming (P7) or 5/1/1 day |
|
|
|
|
|
|
| programming (P3) is available |
19 | | | (On) AS Heat | OFF |
| Automatic Schedule for heat mode. | |
20 | | | (On) AS Cool | OFF |
| Automatic Schedule for cool mode. | |
21 | | MS | (On) FA Heat | OFF |
| Fast Heat option may be disabled by | |
|
|
|
|
|
|
| selecting OFF. NA to SS config. |
22 | HP2 | | (On) FA Cool | OFF |
| Fast Cool option may be disabled by | |
|
|
|
|
|
|
| selecting OFF. NA to SS config. |
|
|
|
|
|
|
| NA to Heat only system. |
23 | | | (OFF) CA |
| On |
| Selects active Comfort Alert On or OFF. |
|
|
|
|
|
|
| Require CA II Module. (Not available on earlier models) |
24 | | | (On) dS | OFF |
| Selects Automatic daylight Savings Time | |
|
|
|
|
|
|
| option On or OFF. |
25 | | | (OFF) Change Filter |
| On |
| Selects Filter |
26 | | | (200 h) Change Filter |
| Change Filter time in 25 hour increments. This | ||
|
|
|
|
|
|
| menu only appears if On is selected in above. |
27 | | | (o) On Cool | (b) On Heat |
| Selects operation of the reversing valve terminal (O/B) | |
|
|
|
|
|
|
| output as an O or B terminal. |
6