White Rodgers 1F95-1280 specifications Installer/Configuration Menu, Mode

Models: 1F95-1280

1 16
Download 16 pages 30.88 Kb
Page 6
Image 6
Mode

INSTALLER/CONFIGURATION MENU

CONFIGURATION MENU

Screen

SS1

HP1

Press

Displayed

Press

or

 

 

Comments

 

Reference

MS2

HP2

key

Factory

to select from

 

Number

 

 

 

(Default)

listed options

 

 

 

 

 

 

 

 

 

 

33

 

 

(05) dF

0 - 09

 

 

Selects Dual Fuel setting using software logic, dF selected On with no

 

 

 

 

 

 

 

 

 

outdoor sensor..

 

 

 

 

 

 

 

 

 

 

34

 

 

(60) Cd

0-99

 

 

 

Selects compressor off delay in seconds, dF selected On

 

 

 

 

 

 

 

 

 

35

 

 

(80) AO

-5 - 79

 

 

Selects Auxiliary Heat cut out temperature.. This item appears if HP1

 

 

 

 

 

 

 

 

 

or HP2 is selected and outdoor sensor is installed and enabled..

 

 

 

 

 

 

 

 

 

36

 

(0) PP

1, 2, 3

 

 

Selects Pre-occupancy purge.. Not available if 4 is 0

 

 

 

 

 

 

 

 

 

 

37

 

(OFF) EC

on

 

 

 

Selects Economizer or Damper Operation (default).. Not available if 4

 

 

 

 

 

 

 

 

 

is 0

 

 

 

 

 

 

 

 

 

 

41

 

(OFF) Change

On

 

 

 

Selects Change UV Lamp feature.

 

 

 

 

UV Lamp

 

 

 

 

 

 

 

 

 

 

 

 

 

 

42

 

350 Days

25-1975

 

 

Change UV Lamp duration days..

 

 

 

 

 

 

 

 

 

 

43

 

OFF

On

 

 

 

Selects Change Filter feature..

 

 

 

 

Change Filter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

44

 

200 Hrs

25-1975

 

 

Change Filter duration hours..

 

 

 

 

 

 

 

 

 

 

1.This control can be configured for:

MS2 Multi-Stage System - No Heat Pump (2 heat/2 cool)

HP1 – Heat Pump with one stage of compressor (2 heat/1 cool)

HP2 – Heat Pump with two stage compressor or two compressor system, Gas or Electric backup; (Dual Fuel see menu item 27) (4 heat/2 cool)

SS1 – Single Stage System and 3 wire zone systems see wiring diagrams..

2.GAS or Electric (ELE) fan operation.. If the heating system requires the thermostat to energize the fan, select ELE.. Select GAS if the heating system energizes the fan on a call for heat.. Note: Resetting the thermostat switches the option to GAS.

3.O/B Terminal selection – Selects the operation of the reversing valve (when item 1 is set to HP1 or HP2 only).. When set to "O" the changeover valve will be energized in COOL to accommodate the majority of heat applica- tions.. If the heat pump requires the changeover valve to energize in HEAT, select "B"..

4.Programs per week – This control can be configured for 7 independent day or 5/1/1 day programming or nonpro- grammable modes.. Default is 7-day mode.. The display indicates "7 Days" as default.. Other options "5 Days" or "0 Days" can be selected.. If "0 Days" is selected for non- programmable mode, the step for EMR will be skipped, as this feature will not be available in this mode..

5.System Switch Configuration (MS2/SS1) – This ther- mostat is configured for Heat and Cool with Auto change- over default (Cool-Off-Heat-Auto).. It can be configured as Heat & Cool (Cool-Off-Heat), or Heat Only (Off-Heat), or Cool Only (Cool-Off)..

When the control is in heat pump configuration (HP1/ HP2), the system switch configuration will have an additional mode available, Em for Emergency Mode..

6.Energy Management Recovery (EMR) – (this step is skipped if configured as non-programmable).. When set to "On" causes the thermostat to start heating or cooling early to make the building temperature reach the program setpoint at the time you specify..

Example: The heating program is 65°F at night and 70° at 7 AM.. If the building temperature is 65°F, the difference is 5°F.. Allowing 5 minutes per °F rise, the thermostat set- point will change to 70° at 6:35 AM.. Cooling allows more time per °F, because it takes longer to reach temperature..

7, 8 & 9.. Cycle Rate Selection – The factory default setting is fast cycle (FA Cr) in all modes (Heat, Cool, Emer).. To change to slow cycling (SL, Cr), press touch keysManual backgroundor Manual backgroundtoggle between FA & SL.. The cycle rates are below:

Mode

Fast rate

Slow rate

Heat (SS1, MS2)

0..6°F

1..5°F

Cool (SS1, MS2)

1..2°F

1..7°F

Heat Pump (HP1, HP2)

1..2°F

1..7°F

Emer Heat (HP1, HP2)

0..6°F

1..7°F

10.Select Compressor Lockout (CL) – Selecting (CL On) will cause the thermostat to wait 5 minutes between cool- ing cycles.. This is intended to help protect the compressor from short cycling.. Some of the newer compressors have a time delay built in and do not require this feature to be activated in the thermostat.. Your compressor manufactur- er can tell you if this lockout feature is already present in their system.. When the thermostat compressor time delay is activated, it will flash the set point for up to five minutes..

11.Select Continuous Backlight (dL) – In low lighting con- ditions, display backlight improves the display contrast. When C terminal is connected, selecting dL On will turn the backlight on continuously.. Selecting dL Off will turn the backlight on momentarily after any key is pressed.. When C terminal is not powered (battery only), dL On enables the momentary backlight whenever a key is pressed..

12.Select Temperature Display Adjustment 5 LO to 5 HI This allows you to adjust the room temperature display by -5°F to +5°F in 1° steps.. Your thermostat was accu- rately calibrated at the factory, however you have the option to change the display temperature value to match the previous thermostat, if you so prefer..

13.Select °F or °C Readout – Changes the display readout to Celsius or Fahrenheit as required..

14.Select Audio Prompting (Beeper) On or Off – Factory default setting is b, On.. If you wish to turn off the beeper select OFF..