White Rodgers 1F97-1271 specifications Installer/Configuration Menu

Models: 1F97-1271

1 8
Download 8 pages 59.17 Kb
Page 4
Image 4
INSTALLER/CONFIGURATION MENU

INSTALLER/CONFIGURATION MENU

To enter the menu: Press the Menu button. Press and hold for 5 seconds the Installer Config button this displays menu item #1 in the table below. Press Manual background to advance to the next menu item or Manual background to return to a previous menu item. Press Manual background or Manual background to change a menu item.

Menu

Reference

Number

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

7

Day

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

Non-

Program-

mable

1

2

*NA 3

*NA 4 5 6 7 8

9

10

11

12

13

14

15

16

 

 

CONFIGURATION MENU

 

Displayed

Press

or

 

 

 

 

 

 

Press

(Factory

to select from

 

Button

Default)

listed options

Comments

 

(GAS)

ELE

 

 

 

GAS setting: furnace controls blower.

 

 

 

 

 

 

ELE setting: thermostat controls blower.

 

Days (7)

5, 0

 

 

 

Selects programming option.

 

PS (4)

2

 

 

 

Selects programming periods per day.

 

Cool, Off,

Cool, Off, Heat,

Selects system switch configuration for heat and cool with

 

Heat, Auto

Off, Heat, Cool, Off

Auto changeover, Heat & Cool, Heat Only or Cool Only.

 

E (On)

OFF

 

 

 

Selects Energy Management Recovery on or off.

 

Cr Heat (FA)

SL

 

 

 

Selects Heat cycle rate Fast (FA) or Slow (SL).

 

Cr Cool (FA)

SL

 

 

 

Selects Cool cycle rate Fast (FA) or Slow (SL).

 

CL (OFF)

On

 

 

 

Selects Compressor lockout ON or OFF.

 

dL (On)

OFF

 

 

 

Selects display light on or off.

 

0

1, 2, 3, 4 HI

Selects temperature display adjustment 1, 2, 3 or 4 degrees

 

(Room temp)

1, 2, 3, 4 LO

high or low.

 

°F

°C

 

 

 

Selects Fahrenheit or Celsius temperature display.

 

b (On)

OFF

 

 

 

Selects beeper on or off.

 

Heat (99)

62-99

 

 

Selects highest Heat setpoint temperature.

 

 

 

 

 

 

Can select 62° to 99°F.

 

Cool (45)

45-82

 

 

Selects lowest Cool setpoint temperature.

 

 

 

 

 

 

Can select 45° to 82°F.

 

Keypad

L, P

 

 

 

Selects keypad lockout full or partial to be set.

 

lockout (L)

Temperature Limit

Activates temperature limit ranges.

 

Keypad

On

 

 

 

Selects keypad lockout on or off.

 

lockout (OFF)

 

 

 

 

 

000000 to 999 Selects keypad lockout combination number if lockout is on. 000 is not a valid selection.

000 Change

On

Select change filter alert time period.

Filter (OFF)

 

 

 

 

 

200 hours

25 to 1975 hours

When set ON, selects time in 25 hour increments.

Change

On

Selects change humidifier pad alert time period

Humidifier

 

 

(OFF)

 

 

 

 

 

100 hours

25 to 1975 hours

When set ON, selects time in 25 hour increments.

* Not Applicable

1)GAS or Electric (ELE) fan operation. If the heating system requires the thermostat to energize the fan, select ELE. Select GAS if the heating system energizes the fan on a call for heat. Note: Resetting the thermostat switches the option to ELE.

2)This control can be configured for 7 independent day or 5/1/1 programming or non-programmable mode. The display indicates "7 Days" as default. The programs per

week can be toggled to "5 Days" or "0 Days" by pressing the Manual background or Manual background keys. A selection of 0 Days for non-program- mable will eliminate the need for EMR, and that step

in the menu will be skipped.

3)Programmable Periods – This control can be configured for 4 or 2 programmable periods per day. The display

indicates "4 PS" in the display as default. The program- mable periods can be toggled by pressing the Manual background or Manual background keys.

4)System Switch Configuration – This thermostat is configured for Heat and Cool with Auto changeover (SYSTEM switch with Cool Off Heat Auto) default. It can also be configured for Heat and Cool (Cool Off Heat), Heat only (Off Heat), and Cool only (Cool Off).

5)Energy Management Recovery – (this step is skipped if configured to be non-programmable).

Energy Management Recovery (E) On causes the thermostat to start heating or cooling early to make the building temperature reach the program setpoint at the time you specify. Heating will start 5 minutes early for every 1° of temperature required to reach setpoint. Example: E On is selected and your heating is pro- grammed to 65° at night and 70° at 7 AM. If the building temperature is 65°, the difference between 65° and 70° is 5°. Allowing 5 minutes per degree, the thermostat set- point will change to 70° at 6:35 AM. Cooling allows more time per degree, because it takes longer to reach temperature.

4

Page 4
Image 4
White Rodgers 1F97-1271 specifications Installer/Configuration Menu