White Rodgers 2061 installation instructions ZONE-AIR Two-WireDAMPER MOTOR, Description

Models: 2061

1 6
Download 6 pages 58.8 Kb
Page 1
Image 1
WHITE-RODGERS

WHITE-RODGERS

2061 ZONE-AIR

Two-Wire DAMPER MOTOR

with Access-Mounting Plate

INSTALLATION INSTRUCTIONS

Operator: Save these instructions for future use!

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.

The Type 2061 Damper Motor provides a low-cost system of zoned temperature control for warm air heating. It is of the two-wire type, and is specially designed for use with a two-wire thermostat with .2 Amp heat anticipator.

Each room or zone requires one damper motor and one thermostat. The thermostat automatically controls the passage of warm air through the duct by operating the

DESCRIPTION

damper motor which is installed on the duct work to each room or zone.

This Damper Motor-Thermostat combination may be in- stalled on present systems for economical conversion to zone heating. It is ideally suited for split-level and ranch- type homes having a warm air heating plant.

Do not exceed the specification ratings.

All wiring must conform to local and national electrical codes and ordinances.

This control is a precision instrument, and should be handled carefully. Rough handling or distorting compo- nents could cause the control to malfunction.

!WARNING

Do not use on circuits exceeding 30 volts. Higher voltage will damage control and could cause shock or fire hazard.

PRECAUTIONS

!CAUTION

To prevent electrical shock and/or equipment damage, disconnect electric power to system, at main fuse or circuit breaker box, until installation is complete.

Do not short out terminals on gas valve or primary control to test. Short or incorrect wiring will burn out heat anticipator and could cause personal injury and/or property damage.

SPECIFICATIONS

All guarantees are void if these specifications are exceeded.

Electrical Ratings: The Damper Motor draws .2 Amp Max. at 25 VAC when in the open position. Auxiliary Contacts: Do not exceed 2.0 Amp at 25 VAC (terminals 2 and 3).

NOTE

Thermostat: Use two-wire thermostat with .2 Amp anticipator.

Timings: From full close to full open - Approximately 45 seconds

From full open to full close - Approximately 60 seconds.

Maximum Duct Size: 300 square inches

Maximum Duct Capacity: 1200 cubic feet per

The Damper Motor draws more than .2 Amp while it

minute.

 

is opening. For this reason, do not use more than the

 

recommended number of damper motors per trans-

 

former as shown on page 4.

WHITE-RODGERS DIVISION

 

PART NO. 37-1499B

EMERSON ELECTRIC CO.

Printed in U.S.A.

9797 REAVIS ROAD

Replaces 37-1499

 

ST. LOUIS, MISSOURI 63123-5398

 

9516

Page 1
Image 1
White Rodgers 2061 installation instructions ZONE-AIR Two-WireDAMPER MOTOR, with Access-MountingPlate, Description