White Rodgers 24A07A-1 installation instructions Type 24A07, Description, precautions

Models: 24A07A-1

1 8
Download 8 pages 18.85 Kb
Page 1
Image 1
Type 24A07

Type 24A07

“Slimline” level-temp

silent operator

(Normally Open)

Installation Instructions

Operator: Save these instructions for future use!

FAILURETO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.

These Level-Temp Silent Operator relays are designed for use on electric heating equipment in conjunction withWhite-Rodgers low voltage thermostats.They are especially suitable for use on baseboards, wall insert heaters, etc. Some models also have an inductive rating to permit them to be used on motor loads where a time delay is desired.

Different models of these Silent Operator relays are available for voltage inputs of 120, 208, 240, 277, 347 or 600 volts. Since these relays are equipped with a self-contained transformer, the supply voltage used must agree with the voltage rating of the relay.

When required, two or more of these Silent Operator relays can

DESCRIPTION

be operated by one low voltage heating thermostat.These Silent Operator relays have been carefully adjusted at the factory. No attempt should be made to adjust them in the field.

If in doubt about whether your wiring is millivolt, line, or low voltage, have it inspected by a qualified heating and air condi- tioning contractor, electrician, or someone familiar with basic electricity and wiring.

Do not exceed the specification ratings.

All wiring must conform to local and national electrical codes and ordinances.

This control is a precision instrument, and should be handled carefully. Rough handling or distorting components could cause the control to malfunction.

precautions

!CAUTION

To prevent electrical shock and/or equipment damage, disconnect electric power to system, at main fuse or circuit breaker box, until installation is complete.

!WARNING

Do not use on circuits exceeding specified voltages. Higher voltages will damage control and could cause shock or fire hazard.

Electrical Data

Switch Action: Single-Pole, Single-Throw, normally open

Thermal: Average time delay – 45 seconds

Ambient Temp.: -20° to 140°F (-24° to 60°C)

specifications

Room Thermostat:

Set adjustable heat anticipator at 0.2 Amps.For fixed anticipa- tion thermostats, use 0.15 to 0.25 Amp. heater.

Type

input

thermostat

A.C. Resistive

A.C. Motor Inductive

Number

voltage /frequency

current

non-inductive

FULL LOAD

LOCKED ROTOR

 

 

 

 

 

 

24A07A-1

120VAC, 60 Hz

0.2A

25A, 3000W, 120V

16A, 120V

96A, 120V

24A07E-1

208VAC, 60 Hz

0.2A

25A, 5200W, 208V

12A, 208V

72A, 208V

24A07G-1

240VAC, 60 Hz

0.2A

25A, 6000W, 240V

12A, 240V

72A, 240V

24A07Z-1

277VAC, 60 Hz

0.2A

22A, 6000W, 277V

________

________

________

________

24A07Z-8

347VAC, 60 Hz

0.2A

17A, 5900W, 347V

________

________

24A07Z-9

600VAC, 60 Hz

0.2A

12A, 7200W, 600V

 

 

Mounting: Mounting tabs with several break-offs for 2, 3 or 4 hole mounting.

 

PART NO. 37-4709D

www.white-rodgers.com

Replaces 37-4709C

www.emersonclimate.com

1209

Page 1
Image 1