Electrical Rating:
Voltage: 24 Volts, (30 Volts Max.), 60 Hz.
Current Rating: 0.23 Amps
Type of Gas
Natural Gas
Pressure Rating: 12 lb. per sq. in. (14” W.C.)
Pressure Regulator Setting:
Adjustable from 2.5 to 5.0" W.C.
(Factory preset for 3.5" W.C.)
Ambient Temperature: -40° to 175°F
Thermocouple:
30 millivolt type
PIPE SIZES/CAPACITIES
Pipe Size
(inches)
Capacity (BTU/hr) at
1” pressure drop across valve
1
2
” x
3
8
1
2
” x
1
2
1
2
” x
3
4
3
4
” x
3
4
100,000
230,000
230,000
280,000
162,000
372,600
372,600
453,600
Nat. Gas
(1000 BTU/cu. ft.,
64 Sp. Gr.)
LP Gas
(2500 BTU/cu. ft.,
1.53 Sp. Gr.)
INLET BOSS
UP OR DOWN
UPRIGHT
LEFT OR RIGHT
Upright, 90° from upright or vertical
NOTE: Control shown may not be identical
to replacement control.
ON
OFF
Figure 1.Gas valve mounting positions
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS ROAD, ST. LOUIS, MO 63123-5398
(314) 577-1300, FAX (314) 577-1517
9999 HWY. 48, Markham, ONT, L3P 3J3
(905) 475-4653, FAX (905) 475-4625 Printed in U.S.A.
PART NO. 37-5825B
Replaces 37-5825A
0024
INSTALLATION INSTRUCTIONS
WHITE-RODGERS

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE

INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY

AND/OR PROPERTY DAMAGE.

The multi-function gas controls combine into a single
package the functions of 3-position gas cock, main gas
valve, pressure regulator and 100% shut-off automatic
pilot. The pilot gas outlet accepts a 14” pilot line connec-
tion.
This model features a slow opening main valve that
provides a softer ignition and E.C.O. connections.
To permit replacement of a variety of valve sizes, some
models are furnished with two reducer bushings (two 34
to 12”). Also included is an E.C.O. jumper wire that allows
this valve to be used on an installation without electrical
cut off device.

Operator: Save these instructions for future use!

DESCRIPTION

SPECIFICATIONS

36C53

Combination Gas Valves

(24 Volt Model)

CONTENTS

Description......................................................... 1
Specifications..................................................... 1
Precautions........................................................ 2
Installation.......................................................... 2
Main Piping Connection
Pilot Gas Connection
Energy Cut Off (E.C.O.) Connection
Thermocouple Connection
System Wiring
Adjustment......................................................... 4
Pilot Gas Adjustment
Pressure Regulator Adjustment
Pilot Lighting Instructions and Precautions........ 5
OFF
PILOT
ON
E.C.O