System Specifications

7.0System Specifications

7.1Technical Data

 

Voltage

3x480V

 

 

 

 

Voltage tolerance

 

 

Normal operation

±15%

 

Normal operation

±10% standard

 

 

±4, 6 8% (programmable)

 

 

 

Input

 

60Hz

Frequency

±6 standard

 

 

±0.5-8% (programmable)

 

 

 

 

Input power factor

load 25% minimum 0.97

 

load 100% minimum 0.99

 

 

 

 

 

 

Current distortion

Max. 5%

 

 

 

 

Voltage

3x480V

 

 

 

 

 

±1% static, symmetrical load

 

Voltage tolerance

±3% static, symmetrical load

 

 

±5% 0-100% load step

 

 

 

 

Voltage distortion

Max. 3%, linear load

 

Max. 5%, non-linear load

 

 

 

 

 

Output

Load power factor

0.9 lead to 0.8 lag

 

 

 

 

Frequency

60Hz (utility synchronized)

 

±0.1% free running

 

 

 

 

 

 

Overload capacity

 

 

Normal operation

200% - 60 seconds

 

Normal operation

125% - 10 minutes

 

Battery operation

150% - 30 seconds

 

Bypass operation

125% - continuous

 

 

 

 

 

0-40°C/32-104°F (Temperatures

 

Ambient temperature

above 25°C/77°F will reduce

 

 

battery life time)

 

 

 

 

Humidity

Max. 95% non-condensing

General

Protection class

NEMA1

 

Safety

UL 1778

 

Emission and Immunity

FCC ClassA

 

Static bypass switch

Built-in

 

Auto restart

Programmable

 

Economy mode

Programmable

 

 

 

990-4049

Installation Guide APC Silcon 240-320kW 480V UPS

75

Page 75
Image 75
American Power Conversion 240-320kW manual System Specifications, Technical Data, Voltage 3x480V, General