External Connection

Working Principle of Dual Utility (2 utility supplies)

 

 

 

Q3

Utility 2

 

 

 

 

Output

 

 

Q10

 

 

 

 

 

 

Q2

 

 

Q1

Utility 2

 

 

 

 

 

 

 

 

 

 

Utility 1

 

 

Utility 1

 

 

 

 

 

APC Silcon UPS

NOTICE!

Max. phase shift between utility 1 and 2: less than ±3.

Refer to section 7.0 System Specifications for frequency tolerance of utility 1 and 2, and voltage. Utility 1 supports the load in normal operation. Utility 2 supports the load through the static and service bypass switch.

Working Principle of Single Utility (1 utility supply)

Q3

Utility 1/2

Output

Q1

Q2

Utility 1/2

APC Silcon UPS

NOTICE!

Refer to section 7.0 System Specifications for frequency and voltage tolerance of utility 1. Utility 1 or 2 supports the load in normal operation or through the static service bypass switch.

990-4049

Installation Guide APC Silcon 240-320kW 480V UPS

19

Page 19
Image 19
American Power Conversion 240-320kW manual Working Principle of Dual Utility 2 utility supplies