Installation
3.0Installation
3.1Requirements on Site
All system parts are accessible from front or top of UPS. Cable entries are accessible from top or bottom. The system may be installed close to walls as long as free space is allowed for system doors to open.
For ventilation and service purposes allow for free space of a minimum of 3 foot above and in front of UPS. Never install systems in direct sunlight.
WARNING!
For safety reasons do not stand on UPS. Keep UPS cabinet surface free of any objects
3.2Dimensions and Weight
3.2.1 Dimensions and Weight of UPS
UPS | Height | Width | Depth | Weight | |
inch/mm | inch/mm | inch/mm | lbs./kgs | ||
| |||||
240kW 480V | 70.86/1800 | 74.80/1900 | 31.50/800 | 4432/2014,5 | |
320kW 480V | 70.86/1800 | 74.80/1900 | 31.50/800 | 4432/2014,5 | |
Cabinet |
| 74.80/1900 in./mm wide |
|
| |
| 70.86/1800 in./mm |
|
|
|
Installation Guide APC Silcon | 9 |