External Connection
Relay Number | Message | Alarm Trigging Events |
|
|
|
2 ## | Bypass Outside | Bypass voltage RMS value outside tolerance |
(X003) | Tolerance | Bypass wave form (fast detector) outside tolerance |
|
| Bypass frequency outside tolerance |
|
|
|
3 ## | Output Outside | Output voltage RMS value outside tolerance |
(X004) | Tolerance | Output wave form (fast detector) outside tolerance |
|
| Output frequency outside tolerance |
|
|
|
4 | System Overload | Output load over 100% |
(X005) |
| Delta inverter current limiter active |
|
| Main inverter current limiter active |
|
|
|
5 (X006) | Fan Fault | Blocked or faulty fan |
|
|
|
6 | High Equipment | Static switch temperature too high |
(X007) | Temperature or | Main inverter failure (temperature too high or fuse blown) |
| Inverter Fuse Blown | Delta inverter temperature too high |
|
| Magnetics temperature too high |
|
| Isolation transformer optional temperature too high |
|
| Battery temperature too high |
|
|
|
7 (X008) | Battery Breaker Box | Battery Breaker Box battery OFF |
| Battery OFF |
|
|
|
|
8 (X009) | Normal Operation | UPS running in normal operation (Status) |
|
|
|
9 ## | Battery Operation | UPS running in battery operation (Status) |
(X010) |
|
|
|
|
|
10 ## | Bypass Operation | UPS running in bypass operation (Status) |
(X011) |
|
|
|
|
|
11 ## | UPS in | |
(X012) |
| (Hot |
|
|
|
12 | Service Bypass | Service bypass switch active |
(X013) | Operation |
|
|
|
|
13 ## | Boost Charge | UPS boost charging on battery |
(X014) | Operation |
|
|
|
|
14 | Battery Voltage Outside | DC voltage too high (shut down) |
(X015) | Tolerance | DC voltage under warning level |
|
| DC voltage too low (shut down) |
|
|
|
15 | Battery Condition Fault | ABM detected battery weak |
(X016) |
| ABM detected defective battery |
|
| (ABM = Advanced Battery Monitor) |
|
|
|
16 ## | Common Fault | All alarms as mentioned above (except relays |
(X017) |
| 8+9+10+11) |
|
| Internal power supply fault |
|
| System locked in operation mode |
|
| Internal memory fault |
|
| Internal communication fault |
|
|
|
##Delay programmable in XXXXXX stack “Common fault delay”. Settings 0,10,20,30 seconds. See section 5.2: System configuration in this guide.