Appendix

8.0Appendix

8.1Table 1. Installation Planning Data

Service (480V

 

 

3 Phase, 3 or 4 wire

Q3

Service Bypass Panel

grounded Wye)

Bypass

input breaker *

Q1

Field

Wiring*

Main Input

Breaker*

UPS Module

Field

Wiring*

Battery Bank

*Supplied by others

Input must be limited to less than 50 kAIC

Installation Planning Data

APC Silcon Series

Load

Q2(480V

3 Phase,

3 or 4

Wire)

 

 

 

 

 

 

 

AC Input (480V)

 

 

Battery System DC

 

AC Output (480V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power rating

 

 

 

 

 

 

 

 

Service

 

 

 

 

 

 

Load side

Heat

 

 

 

Source

P (kW)

I (A)

 

Min. Input

Over-

 

Full

INom

 

IMax

 

Over-

Rejec-

kW

kVA

Pf

V

Hz

Nom.

Max.

Nom.

Max.

 

Cable

current

Vn

load

Disch

 

Disch

In

current

tion

 

(per phase)

Protection*

(Vdc)

P(kW)

(A)

 

(A)

(A)

Protection*

kBTU/hr

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120

120

1

480

60

126.8

140.0

152.5

168.0

 

1 x 4/0

225AT

2x384

127.0

166

 

194.8

144.0

200AT

23.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

160

160

1

480

60

167.5

186.0

201.5

224.0

 

1 x 350mcm

300AT

2x384

168.8

220

 

258.9

192.0

250AT

25.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

240

240

1

480

60

252.9

280.0

304.2

336.0

 

1 x 700mcm /

450AT

2x384

252.1

328

 

386.7

289.0

400AT

44.0

 

 

 

 

 

 

 

 

 

 

2 x 4/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

320

320

1

480

60

334.4

373.0

402.2

448.0

 

2 x 350mcm

600AT

2x384

335.4

437

 

514.4

385.0

500AT

49.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

400

1

480

60

415.8

460.0

500.1

560.0

 

2 x 350mcm

700AT

2x384

421.9

549

 

647.1

482.0

600AT

35.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

500

1

480

60

519.2

574.0

624.5

700.0

 

2 x 700 /

900AT

2x384

525.8

685

 

806.4

602.0

800AT

65.5

 

 

 

 

 

 

 

 

 

 

3 x 350mcm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes

 

 

 

 

 

1

2

 

3,6,8,A,B,C,D

4,7,9,D

5

 

6,10

 

6,11

 

4,6,8,D

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Not provided by APC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

1.Nominal (Nom) Input current based on rated load.

2.Maximum (Max:) Input current based on full battery recharge + nominal load.

3.Recommendation: Input and Output cables run in separate conduits.

4.Suggested Input overcurrent protection based on continuous full load

Maximum Input current. Suggested Load Side Overcurrent Protection based on Nominal current. Breakers sized per NEC 220-3 and NEC 240-3(b). 80% rated breakers assumed. Trip rating based on

NEC 240-6(a) standard breaker sizes.

5.Nominal battery voltage assumed to be 2.0 volts/cell (lead technology).

6.Recommendation: All cables should be sized in accordance with NEC 210-19 FPN No. 4 branch feeder voltage drop of 3%. Voltage drop not considered in above chart. Application

990-4049

76

Installation Guide APC Silcon 240-320kW 480V UPS

Page 76