Appendix
8.0Appendix
8.1Table 1. Installation Planning Data
Service (480V |
|
|
3 Phase, 3 or 4 wire | Q3 | Service Bypass Panel |
grounded Wye) |
Bypass |
input breaker * |
Q1 |
Field |
Wiring* |
Main Input |
Breaker* |
UPS Module |
Field |
Wiring* |
Battery Bank
*Supplied by others
Input must be limited to less than 50 kAIC
Installation Planning Data
APC Silcon Series
Load
Q2(480V
3 Phase,
3 or 4
Wire)
|
|
|
|
|
|
| AC Input (480V) |
|
| Battery System DC |
| AC Output (480V) |
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Power rating |
|
|
|
|
|
|
|
| Service |
|
|
|
|
|
| Load side | Heat | ||
|
|
| Source | P (kW) | I (A) |
| Min. Input | Over- |
| Full | INom |
| IMax |
| Over- | Rejec- | |||
kW | kVA | Pf | V | Hz | Nom. | Max. | Nom. | Max. |
| Cable | current | Vn | load | Disch |
| Disch | In | current | tion |
| (per phase) | Protection* | (Vdc) | P(kW) | (A) |
| (A) | (A) | Protection* | kBTU/hr | |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
120 | 120 | 1 | 480 | 60 | 126.8 | 140.0 | 152.5 | 168.0 |
| 1 x 4/0 | 225AT | 2x384 | 127.0 | 166 |
| 194.8 | 144.0 | 200AT | 23.2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
160 | 160 | 1 | 480 | 60 | 167.5 | 186.0 | 201.5 | 224.0 |
| 1 x 350mcm | 300AT | 2x384 | 168.8 | 220 |
| 258.9 | 192.0 | 250AT | 25.6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
240 | 240 | 1 | 480 | 60 | 252.9 | 280.0 | 304.2 | 336.0 |
| 1 x 700mcm / | 450AT | 2x384 | 252.1 | 328 |
| 386.7 | 289.0 | 400AT | 44.0 |
|
|
|
|
|
|
|
|
|
| 2 x 4/0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
320 | 320 | 1 | 480 | 60 | 334.4 | 373.0 | 402.2 | 448.0 |
| 2 x 350mcm | 600AT | 2x384 | 335.4 | 437 |
| 514.4 | 385.0 | 500AT | 49.1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
400 | 400 | 1 | 480 | 60 | 415.8 | 460.0 | 500.1 | 560.0 |
| 2 x 350mcm | 700AT | 2x384 | 421.9 | 549 |
| 647.1 | 482.0 | 600AT | 35.9 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
500 | 500 | 1 | 480 | 60 | 519.2 | 574.0 | 624.5 | 700.0 |
| 2 x 700 / | 900AT | 2x384 | 525.8 | 685 |
| 806.4 | 602.0 | 800AT | 65.5 |
|
|
|
|
|
|
|
|
|
| 3 x 350mcm |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Notes |
|
|
|
|
| 1 | 2 |
| 3,6,8,A,B,C,D | 4,7,9,D | 5 |
| 6,10 |
| 6,11 |
| 4,6,8,D | 12 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
* Not provided by APC |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Notes:
1.Nominal (Nom) Input current based on rated load.
2.Maximum (Max:) Input current based on full battery recharge + nominal load.
3.Recommendation: Input and Output cables run in separate conduits.
4.Suggested Input overcurrent protection based on continuous full load
Maximum Input current. Suggested Load Side Overcurrent Protection based on Nominal current. Breakers sized per NEC
NEC
5.Nominal battery voltage assumed to be 2.0 volts/cell (lead technology).
6.Recommendation: All cables should be sized in accordance with NEC
76 | Installation Guide APC Silcon |