External Connection

Principle diagram

All switch gear switches

must be provided with trip function

Utility 2

Q3

 

Input

 

 

Q10

UPS

 

Output

Trip function

 

 

Utility 1

Input

EPO

Q2

Q1

 

X001

Trip function

 

 

 

Trip function

 

 

 

 

 

 

EPO SW

 

Trip function

 

 

 

External bat-

 

 

 

tery cabinet

 

 

 

or battery room

 

 

All battery breakers in external battery cabinets or

battery room must be provided with trip function

For tripping of all battery breaker and switch gear switches

User-supplied electronics

Output

Load

990-4049

Installation Guide APC Silcon 240-320kW 480V UPS

43

Page 43
Image 43
American Power Conversion 240-320kW manual Ups, Principle diagram