External Connection

4.4Relay Board

Relays

All relays are “fail safe”: In alarm modes, relay coil will be de-energized.

Relay shown in alarm position

1

Maximum load: 8.0A

– 250VAC

2

0.3A

– 60VDC

 

3Minimum load: 0.05A – 6VAC 0.05A – 6VDC

4.4.1Relay Board Functions

NOTICE!

If “communication to controller lost” alarm is active, ALL relays will indicate failure.

Relay Number

Message

Alarm Trigging Events

 

 

 

1 ##

Utility Outside

Utility voltage RMS value outside tolerance

(X002)

Tolerance

Utility wave form (fast detector) outside tolerance

 

 

Utility frequency outside limits

 

 

 

990-4049

Installation Guide APC Silcon 240-320kW 480V UPS