Options/Accessories
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 63
7
8 seismic angles
6.2.1 Mounting Seismic Anchoring
Drill 16 holes for Ø10mm bolts at installation site according to dimensioned sketch.
With the holes drilled in the UPS, position the system correctly and slide the 8 seismic
anchoring angles into the bars (see illustration above). Tighten the angles in the holes, using
bolts and plain washers.
NOTICE!
Tighten all bolts in all 8 angles to the floor. Floor bolts not supplied