American Power Conversion 240-320kW Separate, Programming Example Change Boost Charge Voltage to

Models: 240-320kW

1 80
Download 80 pages 59.64 Kb
Page 50
Image 50

Programming

Parameter

Setting*

Comments

 

 

 

APM*** Mode Active

Disabled

Use only in parallel systems.

 

Redundant +1

Disabled: APM*** off.

 

Parallel +1

Redundant +1: Redundant operation with one unit

 

 

being inactive in parallel system

 

 

Parallel +1: Redundant operation with all units in

 

 

operation.

 

 

 

APM Test Mode Active

YES, NO

YES, if APM*** test mode is active

 

 

 

Battery Connection

Common,

Common: if common battery is used in parallel

 

Separate

system.

 

 

Separate: if separate battery is used

 

 

 

*Bold text refers to standard factory setting **Advanced Battery Monitor

***Advanced Power Management

5.2.1 Programming Example - Change Boost Charge Voltage to 446V

NOTICE!

Change charge voltages, battery warning limit, shut down voltages and high battery temperature limit by entering the actual value. See example above.

990-4049

50

Installation Guide APC Silcon 240-320kW 480V UPS

Page 50
Image 50
American Power Conversion 240-320kW manual Separate, Programming Example Change Boost Charge Voltage to