External Connection

4.8.2 Emergency Power Off (EPO) for UPS

UPS systems installed in a computer room MUST have external batteries with EPO trip- function in Battery Breaker Box and in switch gear.

System Configuration for Dual Utility

Q3

Utility 2

Load

User-supplied external PSU for tripping of battery breakers in external battery cabinet or battery room and switch gear switches.

Q10

Input

UPS Output

Utility 1

Input

Q1

Q2

External DC

Dual Utility Matrix

DC

Utility 2

Utility 1

Possible UPS operation

Tripping

Note

 

 

 

modes

Supply

 

 

 

 

 

 

 

0

0

0

Off

0

Nothing to trip

 

 

 

 

 

 

0

0

1

X

 

Under

 

 

 

 

 

installation only

 

 

 

 

 

 

0

1

0

Bypass operation only

1

 

 

 

 

 

 

 

0

1

1

Bypass operation only

1

 

 

 

 

 

 

 

1

0

0

Battery operation only

1

 

 

 

 

 

 

 

1

0

1

Normal/battery operation

1

 

 

 

 

 

 

 

1

1

0

Bypass/battery operation

1

 

 

 

 

 

 

 

1

1

1

Normal/bypass/battery

1

 

 

 

 

operation

 

 

 

 

 

 

 

 

990-4049

44

Installation Guide APC Silcon 240-320kW 480V UPS

Page 44
Image 44