External Connection

WARNING!

Supply the UPS from grounded 3-wire/4-wire WYE service.

NOTICE!

Ensure correct phase rotation of input voltage.

NOTICE!

Keep UPS input and output conductors in separate conduits.

NOTICE!

Keep AC and DC conductors in separate conduits.

NOTICE!

Keep batteries 1 and 2 (DC conductors) in separate conduits.

WARNING!

Keep UPS power conductors and UPS control wiring in separate conduits.

4.1.2 Seperation of AC from DC1 and DC2

Use the 2 pieces of polycarbonate (supplied with the UPS) to separate AC from DC1 and DC2. Standard length of polycarbonate adjusted for top cable entry. Adjust length of polycarbonate to fit bottom entry where applicable.

Polycarbonate

Polycarbonate

990-4049

16

Installation Guide APC Silcon 240-320kW 480V UPS

Page 16
Image 16