Programming

5.0 Programming

Below table shows operating parameters programmable from keyboard. Only qualified users should amend programming parameters.

5.1Parameters

Parameter

Setting*

 

 

 

Comments

 

 

 

 

 

 

 

Bypass operation

YES, NO

YES will switch the system into bypass

 

 

mode***

 

 

 

 

 

 

 

 

 

 

 

Language

GB, D, F, DK, S, SF,

Languages of text in display

 

NL, PL, CZ, E, P, SK,

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Autostart

YES, NO

Automatic restart by utility return (1 min. delay).

 

 

Ensures quick battery recharge.

 

 

 

 

 

 

 

Remote shutdown active

YES, NO

Shutdown of UPS by remote signal when in

 

 

battery operation. Saves battery energy.

 

 

 

 

 

 

 

Remote shutdown

HIGH, LOW

Nature of remote shutdown signal level

 

 

 

 

 

 

Remote shutdown time

0, 1, 2, 3, 4, 5, 6, 7, 8, Time delay on remote shutdown of UPS

 

9, 10 min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery capacity test

Initiates back-up time check. Time measured

 

 

from start until it reaches low DC warning level

 

 

(See User Guide, section 6.0).

 

 

 

 

 

 

 

Battery monitor test **

Initiates checks of battery condition by 25%

 

 

discharging.

 

 

 

 

 

 

 

 

 

 

 

Automatic battery test**

OFF, 3,6 months

Activates the battery monitor test in cyclic

 

 

intervals.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery monitor reset**

Press the

 

.

and

 

 

key to reset alarm

 

 

 

 

 

 

 

 

 

 

 

 

(flashing light)

 

 

 

 

 

 

 

 

 

 

 

Boost charge

YES, NO

YES results in boost charge (10 hours)

 

 

 

 

 

 

 

Autoboost charge

YES, NO

YES results in boost charge after battery

 

 

operation (10 hours).

 

Enter new date

YYMMDD

Set to local date

Enter new time

HHMMSS

Set to local time (24 hour clock)

*Factory settings in bold

**For stystems with avctive Battery Monitor only

***Do not leave system running in bypass mode (static bypass) for extended periods of time, as batteries are not recharged in bypass mode.

990-4049

46

Installation Guide APC Silcon 240-320kW 480V UPS

Page 46
Image 46