White Rodgers 50A55-438 installation instructions Timing Specifications

Models: 50A55-438

1 8
Download 8 pages 62.95 Kb
Page 2
Image 2
SPECIFICATIONS

SPECIFICATIONS

ELECTRICAL RATINGS [@ 77°F (25°C)]:

Input Voltage: 25 VAC, 50/60 Hz

Max. Input Current @ 25 VAC: 0.45 amp

Relay Load Ratings:

Valve Relay: 1.5 amp @ 25 VAC, 50/60 Hz, 0.6 pf

Ignitor Relay: 6.0 amp @120 VAC, 50/60 Hz, (resistive)

Flame Current Requirements:

Minimum current to insure flame detection: 1 μa DC*

Maximum current for non-detection: 0.1 μa DC*

Maximum allowable leakage resistance: 100 M ohms

*Measured with a DC microammeter in the flame probe lead

OPERATING TEMPERATURE RANGE:

-40°to 175°F (-40°to 80°C)

HUMIDITY RANGE:

5% to 93% relative humidity (non-condensing)

MOUNTING:

 

Surface mount multipoise

 

TIMING SPECS: (@ 60 Hz**)

 

 

maximum

Flame Establishing Time:

0.8 sec

Flame Failure Response Time:

2.0 sec

**At 50 Hz, all timing specifications should be increased by 20%.

Gases Approved: Natural, Manufactured, Mixed, Liquefied Petroleum, and LP Gas Air Mixtures are all approved for use.

TIMING SPECIFICATIONS

(All times are in seconds, unless noted otherwise)

 

50A55-438

 

 

PRE-PURGE

0

 

 

TRIAL FOR IGNITION

4

PERIOD

 

IGNITION ACTIVATION

1

PERIOD

 

RETRIES

2 times

VALVE SEQUENCE

12

PERIOD

 

INTERPURGE

60

 

 

POST-PURGE

5

 

 

LOCKOUT TIME

300

 

 

DELAY TO HEAT ON

45

 

 

DELAY TO HEAT OFF

60/100/

140/180*

 

 

 

DELAY TO COOL ON

2

 

 

DELAY TO COOL OFF

0/80*

 

 

MINIMUM IGNITOR

11

WARM-UP

 

 

 

MAXIMUM IGNITOR

21

WARM-UP

 

INITIAL IGNITOR WARM-

17

UP (1st 64 attempts)

 

HUMIDIFIER

YES

 

 

ELECTRONIC AIR

YES

CLEANER

 

 

 

*These times will vary depending on option switch position. The control is factory-set at 0 sec. delay to cool off and 100 sec. delay to heat off. See OPERATION section for further information.

2

Page 2
Image 2
White Rodgers 50A55-438 installation instructions Timing Specifications