White Rodgers 50A55-438 Typical System Wiring Table, Terminal, System Component, Connection, Type

Models: 50A55-438

1 8
Download 8 pages 62.95 Kb
Page 5
Image 5
TYPICAL SYSTEM WIRING TABLE

TYPICAL SYSTEM WIRING TABLE

50A55

TERMINAL

SYSTEM COMPONENT

TERMINAL

TYPE

CONNECTION

W

 

low voltage thermostat W terminal (or equivalent)

G

Terminal

low voltage thermostat G terminal (or equivalent)

R

block with

low voltage thermostat R terminal (or equivalent)

Y

captive

low voltage thermostat Y terminal (or equivalent)

 

screws

(2nd wire from Y terminal goes to 24 VAC HOT side of

 

 

compressor contactor coil)

C

 

24 VAC COMMON side of compressor contactor coil

MV (2 terminals)

 

gas valve (both gas solenoids are connected in parallel)

TR

 

24 VAC transformer (low voltage COMMON side)

TH

 

24 VAC transformer (low voltage HIGH side)

FP

12-pin

flame sensor probe*

PS

connector

pressure switch INPUT

HLI

& harness

high limit INPUT

HLO

 

high limit OUTPUT

GND

 

MUST BE RELIABLY GROUNDED TO CHASSIS

(3 unused terminals)

 

 

 

 

 

IND

 

inducer HOT side

IGN

4-pin

ignitor HOT side

IND N

connector

inducer NEUTRAL side

& harness

IGN N

ignitor NEUTRAL side

 

 

 

 

COOL

spade terminal

circulator blower COOL SPEED terminal

 

 

 

HEAT

spade terminal

circulator blower HEAT SPEED terminal

 

 

 

PARK (2 terminals)

spade terminal

unused circulator blower terminals

 

 

 

LINE

spade terminal

input voltage (120 VAC) HOT side

 

 

 

XFMR

spade terminal

24 VAC transformer line voltage HOT side

 

 

 

HUM (optional)

spade terminal

humidifier HOT side

 

 

 

EAC (optional)

spade terminal

electronic air cleaner HOT side

 

 

 

CIR N

spade terminal

circulator blower NEUTRAL terminal

 

 

 

LINE N

spade terminal

input voltage (120 VAC) NEUTRAL side

 

 

 

XFMR N

spade terminal

24 VAC transformer line voltage NEUTRAL side

 

 

 

HUM N (optional)

spade terminal

humidifier NEUTRAL side

 

 

 

EAC N (optional)

spade terminal

electronic air cleaner NEUTRAL side

 

 

 

* maximum recommended flame probe wire length is 36 inches.

5

Page 5
Image 5
White Rodgers 50A55-438 installation instructions Typical System Wiring Table, Terminal, System Component, Connection, Type