SYSTEM LOCKOUT AND
DIAGNOSTIC FEATURES
SYSTEM LOCKOUT FEATURES
When system lockout occurs, the gas valve is
(System lockout will never override any precautionary features.)
To reset the control after system lockout, do one of the following:
1.Interrupt the call for heat or cool at the thermostat for at least one second but less than 20 seconds (if flame is sensed with the gas valve
2.Interrupt the 24 VAC power at the control for at least one second. You may also need to reset the flame rollout sensor switch.
3.After one hour in lockout, the control will automatically reset itself.
DIAGNOSTIC FEATURES
The 50A55 control continuously monitors its own operation and the operation of the system. The LED light on the control will flash slowly (one flash per second) if there are no failures and no call for heat. If there is a call for heat, the LED will flash quickly (one flash per
If the sensed failure is in the system (external to the control), the LED will flash in the following
2 flashes, then pause | System lockout (no flame) |
3 flashes, then pause | Pressure switch problem |
4 flashes, then pause | Thermal protection device open |
5 flashes, then pause | Flame sensed with gas valve off |
6 flashes, then pause | 115 Volt AC power reversed/im- |
| proper ground |
7 flashes, then pause | Gas valve circuit error |
8 flashes, then pause | Low flame sense signal |
The LED will also flash once at