OPERATION
OPTION SWITCHES
The option switches on the
OPTION SWITCH POSITIONS
COOL delay- | Set switch | |
| #1 | |
45 sec.* |
| On |
90 sec. |
| Off |
|
| |
|
| |
HEAT delay- | Set switch | |
| #2 | |
30 sec.* |
| On |
45 sec. |
| Off |
|
| |
|
|
|
HEAT delay- | Set switch | |
#3 | #4 | |
60 sec. | On | On |
90 sec. | Off | On |
120 sec. | On | Off |
180 sec.* | Off | Off |
* Factory setting
HEAT MODE
In a typical system, a call for heat is initiated by closing the thermostat contacts. This starts the 50A65 control’s heating sequence. The inducer blower and optional humidifier are energized and the 768A silicon nitride ignitor is powered within one second.
This control has an adaptive algorithm that reduces the ignitor temperature to slightly greater than the minimum temperature required to ignite gas in each particular application. The control measures the line voltage and determines an initial ignitor temperature setting based on the measurement. After each successful ignition, the control lowers the ignitor temperature slightly for the next ignition attempt. The control continues to lower the ignitor temperature until ignition does not occur, and the control goes into retry mode. For the second attempt to ignite gas within the same call for heat, the control increases the ignitor temperature to the value it was on the third previous successful ignition. After ignition is successful, the control sets the ignition temperature at this value for the next 255 calls for heat, after which the control repeats the adaptive algorithm. The control is constantly making adjustments to the ignitor temperature to compensate for changes in the line voltage.
The 80 VAC Silicon Nitride ignitor manufactured by White- Rodgers must be used. These ignitors are specially designed to operate with the 50A65’s adaptive ignition routine to ensure the most efficient ignitor temperature.
At the end of the ignitor
begins and the inducer blower remains energized to purge the system for 5 seconds. When the purge is complete, the inducer blower and humidifier are
The “retry” sequence provides a
If flame is detected, then lost, the 50A65 control will repeat the initial ignition sequence for a total of four “recycles”. After four unsuccessful “recycle” attempts, the control will go into system lockout.
If flame is established for more than 10 seconds after ignition, the 50A65 controller will clear the ignition attempt (or retry) counter. If flame is lost after 10 seconds, it will restart the ignition sequence. This can occur a maximum of 11 times before system lockout.
A momentary loss of gas supply, flame blowout, or a shorted or open condition in the flame probe circuit will be sensed within 2.0 seconds. The gas valve will
If the control has gone into system lockout, it may be possible to reset the control by a momentary power interruption of ten seconds or longer. Refer to SYSTEM LOCKOUT FEATURES.
COOL MODE
In a typical system, a call for cool is initiated by closing the thermostat contacts. This energizes the 50A65 control and the compressor. The cool
MANUAL FAN ON MODE
If the thermostat fan switch is moved to the ON position, the circulator fan (cool speed) and optional electronic air cleaner are energized. When the fan switch is returned to the AUTO posi- tion, the circulator fan and electronic air cleaner (optional) are