SPECIFICATIONS
ELECTRICAL RATINGS [@ 77°F (25°C)]: | OPERATING TEMPERATURE RANGE: | |
Input Voltage: 25 VAC 50/60 Hz | ||
Max. Input Current @ 25 VAC: 0.45 amp | HUMIDITY RANGE: | |
Relay Load Ratings: | 5% to 93% relative humidity | |
Valve Relay: | 1.5 amp @ 25 VAC 50/60 Hz 0.6 pf | MOUNTING: |
Ignitor Relay: | 2.0 amp @ 120 VAC 50/60 Hz | Surface mount multipoise |
| (resistive) | Timing Specs: (@ 60 Hz**) |
Inducer Relay: 2.2 |
| maximum |
Circulator Relay: 14.5 | Flame Establishing Time: | 0.8 sec |
Flame Current Requirements: | Flame Failure Response Time: | 2.0 sec |
|
|
Minimum current to insure flame detection: 0.25 µa DC*
Maximum current for
Maximum allowable leakage resistance: 100 M ohms *Measured with a DC microammeter in the flame probe lead
**At 50 Hz, all timing specifications should be increased by 20%
Gases Approved:Natural, Manufactured, Mixed, Liquified Petroleum, and LP Gas Air Mixtures are all approved for use.
TIMING SPECIFICATIONS
(All times are in seconds, unless noted otherwise
Event | Definition |
|
|
|
|
The period of time intended to allow for the dissipation of any unburned | 15 | |
| gas or residual products of combustion at the beginning of a furnace |
|
| operating cycle prior to initiating ignition |
|
|
|
|
Trial for Ignition | The period of time between initiation of gas flow and the action to | 4 |
Period (TFI) | shut off the gas flow in the event of failure to establish proof of the |
|
| supervised ignition source or the supervised main burner flame. |
|
Ignition Activation | The period of time between energizing the main gas valve and | 4 |
Period (IAP) | deactivation of the ignition means prior to the end of TFI |
|
Retries | The additional attempts within the same thermostat cycle for ignition | 4 times |
| when the supervised main burner flame is not proven within the first |
|
| trial for ignition period. |
|
Valve Sequence | Valve sequence period equals 4 seconds trial for ignition period x | 20 |
Period | (1 initial try + 2 retries) + 12 seconds. |
|
Interpurge | The period of time intended to allow for the dissipation of any unburned | 15 |
| gas or residual products of combustion between the failed trial for |
|
| ignition and the retry period. |
|
The period of time intended to allow for the dissipation of any unburned | 5 | |
| gas or residual products of combustion at the end of a furnace burner |
|
| operating cycle. |
|
Lockout Time | ANSI standard rated module timing. | 250 |
|
|
|
Heat | The period of time between proof of the supervised main burner flame | 45 |
| and the activation of the blower motor at Heat speed. |
|
Heat | The period of time between the loss of a call for heat and the | 60/90/120/180 |
| deactivation of the blower motor at Heat speed. |
|
|
|
|
Cool | The period of time after a thermostat demand for cool before energizing | 2 |
| the circulator blower motor at Cool speed. |
|
Cool | The period of time between the loss of a call for cool and the | 2/45 |
| deactivation of the blower motor at Cool speed. |
|
Ignitor | The length of time allowed for the igniter to heat up prior to the initiation | 20 |
| of gas flow. |
|
Auto Reset | After one (1) hour of internal or external lockout, the control will auto- | 60 minutes |
| matically reset itself and go into an auto restart purge for 60 seconds. |
|
Humidifier |
| Yes |
|
|
|
Electronic Air Cleaner |
| Yes |
|
|
|
*This time will vary depending on option switch position. The control is factory set at 90 seconds HEAT