12. DUCTS AND REGISTER MEASUREMENTS

 

 

 

 

(sample calculations)

 

 

 

SIMPLIFIED METHOD

 

 

WARM AIR SYSTEM INSTALLATION

 

 

DISTRIBUTION SYSTEM

 

 

 

 

 

 

Ducts size (heat)

 

 

 

 

HOUSE DIMENSIONS

 

 

 

 

 

 

 

Example: 28 x 40 bungalow: 1,120 sq. ft.

 

 

 

4 inch outlet

reduce by 1”

 

 

 

 

 

 

 

 

 

 

 

 

 

5 inch outlet

reduce by 2”

Always by 8” thick

 

 

28 x 40 x 8: 8,960 cu. ft. x 1.8 Ch. air/hr:

16,128 Btu

 

 

 

 

 

 

 

 

6 inch outlet

reduce by 3”

 

 

 

Exposed walls:

 

 

 

N.B.: The main duct must

be reduced every 2

 

 

40 + 40 + 28 + 28: 136 x 8: 1,088 cu. ft. x 22:

23,936 Btu

 

 

outlets.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number of windows:

 

 

 

 

 

 

 

 

 

12 of 3 x 4: 144 x 60:

8,640 Btu

 

 

Ducts specifications (heat)

 

 

 

 

 

 

 

 

Number of doors:

 

 

 

Dimensions

Length Elbow

Average equivalence

 

 

 

 

 

 

 

2 x 3 x 7: 42 x 100:

4,200 Btu

 

 

4”

10’

1 x 90o

Max 4,000 Btu

 

 

 

 

5”

10’

1 x 90o

Max 6,000 Btu

 

 

 

52,904 Btu

 

 

6”

10’

1 x 90o

Max 7,000 Btu

 

 

Non-insulated basement: 25%

 

 

 

 

 

 

 

 

 

Insulated basement: 15%

7,906 Btu

 

 

 

 

 

 

 

 

or 54 Btu per sq. ft.

60,840 Btu

 

 

 

 

 

 

 

 

DAMPER

 

 

 

 

 

FOR ELECTRIC ELEMENTS 80%:48,672 Btu or 14,28 kW

 

 

 

 

 

 

 

 

TO BE ADDED:House 1 1/2 floor = 25%

 

 

 

For a 4” warm air outlet: 2” x 10” damper

 

 

House 2 floors = 40%

 

 

 

 

 

 

 

 

 

For a 5” warm air outlet: 2” x 12” damper or 4” x 10”

 

 

 

 

 

 

 

 

BEDROOM (for example: 12 x 12)

 

 

 

For a 6” warm air outlet: 2” x 14” damper or 4” x 12”

 

 

 

 

 

 

 

12 x 12 x 8: 1,152 cu. ft. x 1.8 Ch. air/hr:

2,074 Btu

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Exposed walls:

 

 

 

 

 

 

 

 

 

12 + 12 x 8: 192 x 22:

4,224 Btu

 

 

 

 

 

 

 

 

Windows:

 

 

 

 

 

 

 

 

 

3 x 4 x 60

720 Btu

 

 

 

 

 

 

 

 

 

7,018 Btu

 

 

 

 

 

 

 

 

 

 

 

30

Page 30
Image 30
White Rodgers G1N 4R9 Ducts And Register Measurements, Damper, Exposed walls, N.B. The main duct must, be reduced every