NOTE:
It is recommended to install an outside air inlet of minimum 4” diameter in the room where the heating appliance is installed (see drawing below). To do so, it is preferable to choose a wall which is not exposed to extreme winds, according to the conditions surrounding your house.
Insulated conduit full lenght
Free air | Fresh air | |
intake | ||
entry | ||
|
Exterior wall
N.B. The owner of the furnace is responsible for the room salubrity in case of negative pressure or temporary negative pressure.
ELECTRICAL CONNECTION
The following instructions do not supersede the local code.
WOOD ONLY
Installed limit control on support provided on proper location of the appliance (two holes are predrilled on the edge of the furnace), and connected to the electrical box along with the transformer. Install the
The switch located on the fan limit control activates high speed operation, in either automatic or manual (continuous operation) modes.
The switch located on the electric unit controls low speed operation, in either ON (continuous operation) or OFF modes.
WARNING: USE FEEDING WIRES SUITABLE FOR 75OC
WOOD/ELECTRIC
The limit control is a manual reset thermostatic captor and is located directly inside the electric element (see WIRING DIAGRAMS). The electric elements must be installed as shown on the diagram. Install the combined limit control on the support provided, at the determined location. The connections must conform to the diagram.
Install the
9