Williams Airsponge installation instructions WIRING Personal Injury Hazard

Models: Airsponge

1 2
Download 2 pages 31.21 Kb
Page 2
Image 2
WIRING

WIRING

Personal Injury Hazard.

Power supply can cause electrical shock. Disconnect power supply before beginning installation.

All wiring must comply the applicable local codes, ordinances and regulations. Make wiring connections according to dehumidifier instructions; otherwise see typical wiring diagram in Figure 2.

Figure 2 - Diagram for

Dehumidifier

ADJUSTMENTS

Humidity Control Adjustment

To maintain optimum humidity control without causing condensation on cold surfaces such as windows, the homeowner must adjust the set point as the outdoor temperate changes.

To reduce the relative humidity, reduce the set point approximately three percent relative humidity every 24 hours. To increase the relative humidity increase the set point approximately three percent relative humidity ever 24 hours.

Set Point Adjustment

Set the humidity set point according to the prevailing outdoor temperature. See table below for recommended settings.

Recommended Humidity Controller Settings

Outdoor Temperature

Recommended Humidity

F

C

Controller Setting

-20

-29

15

-10

-23

20

0

-18

25

+10

-12

30

+20

-7

35

>+20

>-7

40

OPERATION AND CHECKOUT

Place the system in operation and observe through at least one complete cycle to make certain that all components are functioning properly.

Page 2
Image 2