Problem: The AC load will not operate, error code shows on digital display and alarm is sounding.

Error

Possible Cause

Solution

E01 Low voltage shutdown because

battery is discharged.

E02 Over-voltage shutdown because

of high input voltage.

E03 The AC product(s) connected are rated at more than the inverter’s continuous power rating; overload shutdown has occurred.

Recharge battery.

Shorten cables or use heavier cables.

Verify the charging system is properly regulated and the battery is 12 V nominal.

Use a product with a power rating within the inverter’s continuous power rating (see Table 3).

E04 The inverter has overheated due to poor ventilation. Overheating shutdown has occurred.

E05 The AC products connected have a surge power that exceeds the Digital Inverter’s surge capability or the AC products connected are short-circuited and shutdown has occurred.

Turn inverter off and allow to cool for 15 minutes. Clear blocked fan or remove objects covering unit.

Move the inverter to a cooler place. Reduce load if continuous operation is required.

The products exceed the inverter’s surge capability. Use a product with a starting surge power within the Digital Inverter’s capability.