WARNING: Shock hazard
Safety requirements mandate that this equipment not be serviced while energized. Power sources for the inverter must be
Equipment Required
•Inverter Enclosure Key (7mm triangle key)
•Small flathead screwdriver
•Wire cutter or scissors to trim cable ties
•Ratchet with 10mm socket or 10mm nutdriver
De-Energize/Isolation Procedure (Shutdown)
WARNING: Shock hazard
The terminals of the PV input may be energized if the arrays are energized. In addition, allow 5 minutes for all capacitors within the enclosure to discharge after disconnecting the Grid Tie Inverter from AC and DC sources.
Use the following procedure to isolate and
1.Turn the main ON/OFF switch (S3) to the OFF position.
2.Open the utility connection circuit breaker.
3.Open the AC disconnect.
4.Open the DC disconnect switch.
5.Install lockout devices on the utility connection circuit breaker, AC and DC disconnect switch.
2 | 153553 |
For use by qualified technicians only