Configuration
975-0170-01-01 3–23
Eqz Volts
Full name Equalization voltage
Configurable setting This setting lets you set the desired equalization voltage. This menu is
displayed only if charger equalization is enabled. Select a setting based on
the battery manufacturer’s recommendation. For more information, see
“Battery Charging Reference” on pageB–1.
You can adjust Eqz Volts settings as follows:
Force Charge
Configurable setting This setting forces the charger to be enabled (On) whenever you have
requalified AC. The default setting for Force Charge is On (enabled).
When to use Turn Force Charge to On if you want to automatically start charging
whenever you connect to a qualified AC input, regardless of whether the
Charger is Enabled or Disabled.
Turn Force Charge to Off if you want charging to be determined only by
whether the Charger is Enabled or Disabled.
Outcome If Force Charge is turned to On, the charger starts whenever you have
qualified AC.
Eqz Volts [15.5V]
Range of values Increment Default
13.5 to 15.5 VDC 0.1 volts 15.5 VDC
Force Charge [On]