Image 6
Installation

Installation

Mounting

NOTE: It is not recommended to locate the fuse block inside the enclosure with the batteries where explosive gases may exist.

Locate the fuse block within 18 inches (45 cm) of the battery. It should be placed in a location where it is easily accessible should the fuse need replacing.

1.Squeeze the clear plastic protective cover and remove it from the fuse block base.

2.Use the fuse block base as a template for location of the four mounting holes. The fuse block should be mounted to a secure surface. Allow at least 6 inches (15 cm) from the fuse contacts to allow for removal without shorting to a grounded object.

3.Use appropriate hardware (not supplied) to mount the fuse block.

X4 holes for #10 screws

2.00"

(50.6 cm)

A

B

B

A

6.250" (158.75 cm)

7.0" (177.8 cm)

1.32"

(33.53 cm)

Figure 2

Fuse Block Dimensional Drawing

(Not to scale)

 

Fuse Block Type

Bolt/Lug Size

 

 

 

TFBxxx (bolt/nut)

 

 

 

 

TFBxxxC (set screw)

A

B

 

 

 

 

 

 

 

TFB 110, 200

3/8-18 bolt with hex nut

5/16-10 bolt with hex nut

 

 

 

 

 

 

 

TFB 300, 350, 400

3/8-18 bolt with hex nut

3/8-18 bolt with hex nut

 

 

 

 

 

 

 

TFB 110C, 200C

#2/0 lugs for #4-2/0 cut cables

5/16-10 bolt with hex nut

 

 

 

 

 

 

 

TFB 300C, 350C, 400C

250 MCM lugs for #4-250 MCM cut cables

3/8-18 bolt with hex nut

 

 

 

 

 

 

 

 

Table 1

 

 

 

 

Bolt and Nut Sizes

 

 