Installation (continued)

Installation (continued)

Cable Installation into Fuse Block (continued)

For Fuse Blocks designed for Ring-lugged Battery Cables (TFBxxx)

NOTE: Do not place anything between the ring-lug on the battery cable and the terminal surface.

A.If necessary, install the ring-lugs (not supplied) onto the battery cables. Ensure the terminal connector’s have a 3/8" diameter opening for placement over the stud connector on the fuse block.

1.Remove the 3/8" hex nut and split washers from the fuse block.

2.Place the cable ring lugs over the 3/8-18 bolt on the fuse block assembly and reinstall the split washer and hex nut.

Cable Installation into Fuse Block (continued) See Figure 4.

3.Tighten the hex nuts to 10-15 ft/lbs.

4.Repeat Steps 2, 3, and 4 for connection to the other end of the fuse block.

3/8-18

3/8-18

bolt

bolt

 

hex nut

Ring-lug on

Battery Cables

Terminal surface

split-split-

washerswashers

hex nut

Ring-lug on

Battery Cables

Terminal surface

Figure 4

Installation for Ring-lugged Battery Cables

8