York 10 SEER 50HZ R22 Physical and Electrical Data, Refrigerant, Unit, Dimensions, Connection

Models: 10 SEER 50HZ R22

1 8
Download 8 pages 29.43 Kb
Page 2
Image 2
Physical and Electrical Data

339293-YTG-C-0208

Physical and Electrical Data

Model

 

H1RA018S78

H1RA024S78

H1RA030S78

H1RA036S78

 

 

 

 

 

 

Unit Supply Voltage

 

 

220 - 240V,

1φ, 50Hz

 

 

 

 

 

Normal Voltage Range 1

 

207 to 253

 

Minimum Circuit Ampacity

9.8

14.6

20.4

20.8

 

 

 

 

 

Max. Overcurrent Device Amps 2

15

25

35

35

Compressor Type

 

Recip

Recip

Recip

Recip

 

 

 

 

 

 

 

Compressor Amps

 

Rated Load

7.4

11.3

15.2

15.5

 

 

 

 

 

 

 

Locked Rotor

53

65

90

82

 

 

 

 

 

 

 

 

 

Crankcase Heater

 

 

No

No

No

No

 

 

 

 

 

 

Fan Motor Amps

 

Rated Load

.5

.5

1.8

1.8

 

 

 

 

 

 

 

Fan Diameter Inches

 

 

18

18

18

18

 

 

 

 

 

 

 

 

 

Rated HP

1/12

1/12

1/4

1/4

Fan Motor

 

 

 

 

 

 

 

Nominal RPM

970

970

900

900

 

 

 

 

 

 

 

 

 

Nominal CFM

1,650

1,650

2,350

2,350

 

 

 

 

 

 

 

 

 

Face Area Sq. Ft.

8.00

8.00

9.15

9.15

Coil

 

 

 

 

 

 

 

Rows Deep

1

1

1

1

 

 

 

 

 

 

 

 

 

Fin / Inches

14

14

16

16

 

 

 

 

 

 

Liquid Line Set OD (Field Installed)

3/8

3/8

3/8

3/8

 

 

 

 

 

Vapor Line Set OD (Field Installed)

3/4

3/4

3/4

3/4

 

 

 

 

 

Unit Charge (Lbs. - Oz.) 3

3 - 13

3 - 14

3 - 12

4 - 11

Charge Per Foot, Oz.

 

0.66

0.66

0.68

0.68

 

 

 

 

 

Operating Weight Lbs.

118

123

135

137

 

 

 

 

 

 

 

1.Rated in accordance with ARI Standard 110, utilization range “A”. 2.Dual element fuses or HACR circuit breaker.

3.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.

All dimensions are in inches. They are subject to change without notice. Certified dimensions will be pro- vided upon request.

 

 

 

 

 

 

Refrigerant

Unit

 

Dimensions

 

Connection

 

 

(Inches)

 

Service Valve

Model

 

 

 

 

 

 

 

 

Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A1

 

B

 

C

Liquid

Vapor

018S78

17

 

35

 

23

 

 

024S78

17

 

35

 

23

3/8”

3/4”

030S78

19

 

35

 

23

 

 

 

 

036S78

19

 

35

 

23

 

 

1.Including Fan Guard

2

Unitary Products Group

Page 2
Image 2
York 10 SEER 50HZ R22 Physical and Electrical Data, Refrigerant, Unit, Dimensions, Connection, Inches, Model, Size