York 291627-YTG-B-0807 warranty Unitary Products Group

Models: 291627-YTG-B-0807

1 32
Download 32 pages 10.64 Kb
Page 14
Image 14

291627-YTG-B-0807

TABLE 9: SIDE SUPPLY AIR BLOWER PERFORMANCE - 230 & 460 VOLT1

MODEL #

 

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE - IWG

 

 

 

 

 

 

 

 

MTR

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

1.10

DNH

CFM

WATTS

CFM

WATTS

CFM

WATTS

CFM

WATTS

CFM

WATTS

CFM

WATTS

CFM

WATTS

CFM

WATTS

CFM

WATTS

CFM

WATTS

CFM

WATTS

(Cooling/

SPD

Heating)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HI

-

-

-

-

-

-

1200

560

1110

537

1019

514

929

491

809

473

-

-

-

-

-

-

030

MED

1110

383

1055

368

999

353

944

338

865

319

785

299

-

-

-

-

-

-

-

-

-

-

 

LOW

998

372

906

333

813

294

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

 

HI

-

-

-

-

-

-

-

-

-

-

1447

754

1360

722

1264

692

1169

663

1073

633

977

603

036

MED

-

-

-

-

1483

682

1420

655

1341

625

1262

596

1183

566

1075

534

966

501

-

-

-

-

 

LOW

1384

625

1336

605

1287

584

1239

564

1167

537

1094

509

1022

482

903

460

-

-

-

-

-

-

 

HI

-

-

-

-

1705

847

1622

818

1535

786

1447

754

1360

722

1364

692

1169

663

1073

633

-

-

042

MED

1610

735

1547

708

1483

682

1420

655

1341

625

1262

596

1183

566

1075

534

-

-

-

-

-

-

 

LOW

1384

625

1336

605

1287

584

1239

564

1167

537

1094

509

-

-

-

-

-

-

-

-

-

-

 

HI

1906

982

1857

960

1809

938

1758

913

1706

888

1648

861

1590

834

1445

783

1301

731

-

-

-

-

048

MED

1734

848

1693

821

1651

794

1595

764

1539

734

1461

693

1382

653

1266

613

-

-

-

-

-

-

 

LOW

1532

700

1508

683

1458

667

1444

643

1404

620

1348

593

1291

566

-

-

-

-

-

-

-

-

060

HI

-

-

2444

1433

2380

1400

2313

1363

2245

1325

2169

1285

2092

1245

1902

1168

1711

1092

1521

1015

-

-

(only

MED

2281

1265

2227

1225

2172

1185

2099

1140

2025

1095

1922

1035

1819

975

1665

915

1512

855

-

-

-

-

575 volts)

LOW

1914

1045

1885

1020

1855

995

1805

960

1754

925

1684

885

1613

945

-

-

-

-

-

-

-

-

060

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(3 tube)

HEAT

1500

245

1500

297

1500

348

1500

400

1500

470

1500

540

1500

610

1500

680

1500

750

1500

820

1500

890

(only 230 &

460 volts)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

060

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(4 & 5 tube)

HEAT

1700

390

1700

443

1700

497

1700

550

1700

620

1700

690

1700

760

1700

830

1700

900

1700

970

-

-

(only 230 &

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460 volts)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

060

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(factory

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setting)

COOL

1800

460

1800

515

1800

570

1800

625

1800

690

1800

755

1800

820

1800

962

1800

1105

-

-

-

-

(only 230 &

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460 volts)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

060

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(field setting)

COOL

2000

640

2000

700

2000

760

2000

820

2000

928

2000

1035

-

-

-

-

-

-

-

-

-

-

(only 230 &

460 volts)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Above data includes allowances for a dry evaporator coil, gas heat exchanger and no filters. For additional pressure drops, refer to Tables 12 and 13.