York 291627-YTG-B-0807 Programmable Thermostat Only, Unit Terminal Strip, 24VOLT TRANSFORMER

Models: 291627-YTG-B-0807

1 32
Download 32 pages 10.64 Kb
Page 17
Image 17
THERMOSTAT

291627-YTG-B-0807

TABLE 13: ADDITIONAL STATIC PRESSURE RESISTANCE 3-1/2 - 5 TON (DNH042 - 060)1

 

 

 

 

 

RESISTANCE, IWG

 

 

 

 

DESCRIPTION

 

 

 

 

 

CFM

 

 

 

 

 

1,100

1,200

1,300

1,400

1,500

 

1,600

1,700

1,800

1,900

2,000

WET EVAPORATOR COIL

.02

.03

.04

.05

.06

 

.07

.07

.08

.09

.09

ECONOMIZER2

.02

.02

.02

.03

.03

 

.04

.04

.04

.05

.05

FILTER FRAME KIT

.04

.04

.05

.05

.06

 

.07

.08

.09

.10

.11

1.Deduct these resistance values from the available external static pressure shown in Table 8, 9, 10, and 11

2.The pressure through the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air duct system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.

THERMOSTAT

UNIT TERMINAL STRIP

** = Minimum wire size of 18 AWG

R

**

R

wire should be used for all

 

 

 

field installed 24 volt wire.

G

 

G

 

 

 

Y

 

Y

 

W

 

W

 

C

 

C

NOTE:

HEAT ANTICIPATOR SHOULD BE SET AT 0.35 AMPS FOR ALL MODELS.

24VOLT TRANSFORMER

PROGRAMMABLE

THERMOSTAT ONLY

FIGURE 3 - TYPICAL FIELD CONTROL WIRING DIAGRAM

CONTACTOR

FIELD-SUPPLIED

DISCONNECT

GROUND

LUG REFER TO ELECTRICAL

DATA TABLES TO SIZE

THE DISCONNECT

THREE PHASE POWER SUPPLY

FIGURE 4 - TYPICAL FIELD POWER WIRING DIAGRAM

Unitary Products Group

17

Page 17
Image 17
York 291627-YTG-B-0807 warranty Programmable Thermostat Only, Unit Terminal Strip, 24VOLT TRANSFORMER