TABLE 2: RATINGS COOLING/GAS HEATING
MODEL | NET COOLING CAPACITY1 | SOUND |
| GAS HEAT CAPACITY / EFFICIENCIES |
| |||||
MBH | SEER3 | RATING | INPUT | OUTPUT | AFUE | 4 | NUMBER OF | TEMP. | ||
DNH | (dbels) | 2 |
| RISE | ||||||
|
|
|
| (MBH) | (MBH) | (%) |
| BURNERS | (°F) RANGE | |
030N03625 | 28.0 | 12.0 | 80 |
| 45 | 36 | 80.2 |
| 2 | 25 - 55 |
030N03646 | 28.0 | 12.0 | 80 |
| 45 | 36 | 80.2 |
| 2 | 25 - 55 |
030N05625 | 28.0 | 12.0 | 80 |
| 70 | 56 | 80.2 |
| 3 | 30 - 60 |
030N05646 | 28.0 | 12.0 | 80 |
| 70 | 56 | 80.2 |
| 3 | 30 - 60 |
036N03625 | 36.0 | 12.0 | 81 |
| 45 | 36 | 80.4 |
| 2 | 25 - 55 |
036N03646 | 36.0 | 12.0 | 81 |
| 45 | 36 | 80.4 |
| 2 | 25 - 55 |
036N05625 | 36.0 | 12.0 | 81 |
| 70 | 56 | 80.2 |
| 3 | 25 - 55 |
036N05646 | 36.0 | 12.0 | 81 |
| 70 | 56 | 80.2 |
| 3 | 25 - 55 |
036N07225 | 36.0 | 12.0 | 81 |
| 90 | 72 | 80.1 |
| 4 | 30 - 60 |
036N07246 | 36.0 | 12.0 | 81 |
| 90 | 72 | 80.1 |
| 4 | 30 - 60 |
042N06525 | 42.0 | 12.0 | 80 |
| 80 | 64 | 80.6 |
| 3 | 25 - 55 |
042N06546 | 42.0 | 12.0 | 80 |
| 80 | 64 | 80.6 |
| 3 | 25 - 55 |
042N09025 | 42.0 | 12.0 | 80 |
| 108 | 87 | 80.8 |
| 4 | 45 - 75 |
042N09046 | 42.0 | 12.0 | 80 |
| 108 | 87 | 80.8 |
| 4 | 45 - 75 |
048N06525 | 48.0 | 12.0 | 84 |
| 80 | 64 | 80.8 |
| 3 | 25 - 55 |
048N06546 | 48.0 | 12.0 | 84 |
| 80 | 64 | 80.8 |
| 3 | 25 - 55 |
048N09025 | 48.0 | 12.0 | 84 |
| 108 | 86 | 80.6 |
| 4 | 35 - 65 |
048N09046 | 48.0 | 12.0 | 84 |
| 108 | 86 | 80.6 |
| 4 | 35 - 65 |
048N11025 | 48.0 | 12.0 | 84 |
| 135 | 107 | 80.5 |
| 5 | 45 - 75 |
048N11046 | 48.0 | 12.0 | 84 |
| 135 | 107 | 80.5 |
| 5 | 45 - 75 |
060N06525 | 59.0 | 12.0 | 84 |
| 80 | 64 | 80.7 |
| 3 | 25 - 55 |
060N06546 | 59.0 | 12.0 | 84 |
| 80 | 64 | 80.7 |
| 3 | 25 - 55 |
060N09025 | 59.0 | 12.0 | 84 |
| 108 | 87 | 80.9 |
| 4 | 35 - 65 |
060N09046 | 59.0 | 12.0 | 84 |
| 108 | 87 | 80.9 |
| 4 | 35 - 65 |
060N11025 | 59.0 | 12.0 | 84 |
| 135 | 107 | 80.2 |
| 5 | 45 - 75 |
060N11046 | 59.0 | 12.0 | 84 |
| 135 | 107 | 80.2 |
| 5 | 45 - 75 |
1.Net Cooling Capacity = ARI 210 standard rating conditions.
2.(dbels) = ARI 270-95
3.Seasonal Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in
4.AFUE = Annual Fuel Utilization Efficiency.
Unitary Products Group | 7 |