REFER TO ELECTRICAL
DATA TABLES TO SIZE
THE DISCONNECT
FIGURE 4 - TYPICAL FIELD POWER WIRING DIAGRAM
TABLE 14: ELECTRICAL DATA
|
| VOLTAGE | COMPRESSOR | COND. | SUPPLY |
| MAX. | MAX. |
|
| |||
MODEL | POWER | LIMITATIONS1 | AIR | MINIMUM | HACR | UNIT | TRANSFORMER | ||||||
|
| FAN | FUSE | ||||||||||
DNA | SUPPLY |
|
|
|
| MOTOR, | BLOWER | CIRCUIT | SIZE, | BREAKER | POWER | SIZE (VA) | |
MIN. | MAX. | RLA | LRA | ||||||||||
|
| FLA | MOTOR | AMPACITY | AMPS2 | SIZE, | FACTOR |
| |||||
|
|
|
|
|
|
| FLA |
|
| AMPS |
|
| |
018 | 187 | 253 | 9.0 | 48.0 | 1.1 | 2.2 | 14.5 | 20 | 20 | .96 | 40 | ||
024 | 187 | 253 | 11.5 | 60.0 | 1.1 | 2.2 | 17.7 | 25 | 25 | .96 | 40 | ||
030 | 187 | 253 | 14.7 | 73.0 | 1.1 | 2.2 | 21.7 | 30 | 30 | .96 | 40 | ||
|
|
|
|
|
|
|
|
|
|
|
|
| |
036 | 187 | 253 | 17.3 | 94.0 | 1.1 | 3.5 | 26.2 | 35 | 35 | .96 | 40 | ||
|
|
|
|
|
|
|
|
|
|
|
|
| |
042 | 187 | 253 | 20.5 | 120.0 | 1.1 | 3.5 | 30.2 | 40 | 40 | .96 | 40 | ||
048 | 187 | 253 | 24.4 | 140.0 | 1.3 | 7.0 | 38.8 | 50 | 50 | .96 | 40 | ||
|
|
|
|
|
|
|
|
|
|
|
|
| |
060 | 187 | 253 | 28.9 | 175.0 | 1.3 | 7.0 | 44.4 | 60 | 60 | .96 | 40 |
1.Utilization range “A” in accordance with ARI Standard 110.
2.Dual element, time delay type.
16 | Unitary Products Group |