York B1CH240, B1CH180 Defrost Sequence Of Operation, Defrost Initiation Times

Models: B1CH240 B1CH180

1 20
Download 20 pages 35.36 Kb
Page 17
Image 17
DEFROST SEQUENCE OF OPERATION

DEFROST SEQUENCE OF OPERATION

These heat pumps have a unique “ambient modified” time-temperature defrost control that automatically adjusts to changes in the outdoor temperature. The defrost control will shorten the defrost initiation time periods above 35° F and will extend the defrost initiation time periods below 35° F. The control is factory set to defrost at 110 minutes (T3), but it can be field adjusted to defrost at 80 minutes (T2) or 50 minutes (T1) in areas with high humidity.

The curve in the Deforst Initation Times Figure shows how defrost initiation times are automatically compensated for changes in outdoor temperature.

EXAMPLE: If the timer is factory set on pin T-3 (110 minutes at 35° F outdoor) and the outdoor temperature climbs to 45° , the time initiation cycle will decrease to every 100 minutes.

If the outdoor temperature drops to 10° F where ice is less likely to form, the 110 minute interval will extend to every 150 minutes.

Two requirements must be met before a defrost cycle can be initiated.

1.The defrost time cycle must be complete.

2.The liquid line temperature must be less than 28° F.

Defrost will terminate when the liquid line sensor reaches 55° F or after 10 minutes. If both or just one circuit defrosts, electric heat is energized.

The defrost time cycle will restart 10 minutes after the start of the defrost cycle even though the liquid sensor terminated defrost after 3 minutes.

During troubleshooting, the defrost time can be reduced to 20 seconds by shorting out the SW1 test pegs on the module. The pegs are 1/2" long, 3/16" apart and are mounted on a white base.

511.06-N3Y

LOCKOUT CONTROL

Any one of four conditions will put the system into a lock-out condition during the heating or cooling mode:

1.The discharge line temperature reaches 255° F (215° F reset) or,

2.The discharge pressure reaches 398 PSIG (310 PSIG reset) or,

3.The suction line freezestat equals 26° F (38° F reset) or,

4.The low-pressure cut-out equals 7 PSIG (22 PSIG reset).

Alock-out will energize the emergency heat light on the thermostat and the red LED light on the unit relay board.Turning the thermostat switch to “Off” then back to “On”, will reset the system.

NOTICE TO OWNER:

If a lockout occurs, check for the following problems before calling a serviceman:

1.Dirty filters.

2.Snow accumulation.

3.Leaf or debris blockage.

After eliminating the problem, attempt to restart the system as follows:

turn the system switch on the thermostat to its “OFF” position for 10 seconds.

turn it back to its original position.

If the unit doesn’t start, call a serviceman.

NOTE: Models with an anti-recycle accessory will have a 5-minute delay before starting.

FIG. 11 - DEFROST INITIATION TIMES

Unitary Products Group

17

Page 17
Image 17
York B1CH240, B1CH180 installation instructions Defrost Sequence Of Operation, Defrost Initiation Times