York B1HP024 THRU 048 HEATING CAPACITIES - 2 TON BHP024, HEATING CAPACITIES - 2-1/2TON BHP030

Models: B1HP024 THRU 048

1 28
Download 28 pages 6.22 Kb
Page 11
Image 11

036-21528-001-A-0303

TABLE 8: HEATING CAPACITIES - 2 TON (BHP024)

CFM

RETURN

CAP1

 

 

OUTDOOR AIR TEMPERATURE, ∞F (72% RH)

 

 

AIR ∞F

& KW

 

 

 

 

 

 

 

 

 

-10

0

10

20

30

40

50

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

MBH

10.216

11.748

13.601

15.843

18.554

21.834

25.801

30.601

 

 

 

 

 

 

 

 

 

 

 

KW

1.214

1.307

1.401

1.494

1.588

1.681

1.775

1.868

 

 

 

 

 

 

 

 

 

 

 

 

 

600

70

MBH

7.317

8.849

10.702

12.944

15.655

18.935

22.902

27.702

 

 

 

 

 

 

 

 

 

KW

1.363

1.456

1.550

1.643

1.737

1.830

1.924

2.017

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

MBH

7.205

8.737

10.590

12.832

15.543

18.823

22.790

27.590

 

 

 

 

 

 

 

 

 

 

 

KW

1.423

1.516

1.610

1.703

1.797

1.890

1.984

2.077

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

MBH

10.206

11.738

13.591

15.833

18.544

21.824

25.791

30.591

 

 

 

 

 

 

 

 

 

 

 

KW

1.227

1.320

1.414

1.507

1.601

1.694

1.788

1.881

 

 

 

 

 

 

 

 

 

 

 

 

 

800

70

MBH

7.307

8.839

10.692

12.934

15.645

18.925

22.892

27.692

 

 

 

 

 

 

 

 

 

KW

1.376

1.469

1.563

1.656

1.750

1.843

1.937

2.030

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

MBH

7.195

8.727

10.580

12.822

15.533

18.813

22.780

27.580

 

 

 

 

 

 

 

 

 

 

 

KW

1.436

1.529

1.623

1.716

1.810

1.903

1.997

2.090

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

MBH

11.377

12.909

14.762

17.004

19.715

22.995

26.962

31.762

 

 

 

 

 

 

 

 

 

 

 

KW

1.339

1.432

1.526

1.619

1.713

1.806

1.900

1.993

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

70

MBH

8.478

10.010

11.863

14.105

16.816

20.096

24.063

28.863

 

 

 

 

 

 

 

 

 

KW

1.488

1.581

1.675

1.768

1.862

1.955

2.049

2.142

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

MBH

8.366

9.898

11.751

13.993

16.704

19.984

23.951

28.751

 

 

 

 

 

 

 

 

 

 

 

KW

1.548

1.641

1.735

1.828

1.922

2.015

2.109

2.202

 

 

 

 

 

 

 

 

 

 

 

 

 

1.These capacities are net capacities - the indoor motor heat has been added. These power inputs are total power inputs - the indoor motor watts have been added.

TABLE 9: HEATING CAPACITIES - 2-1/2 TON (BHP030)

CFM

RETURN

CAP1

 

 

OUTDOOR AIR TEMPERATURE, ∞F (72% RH)

 

 

AIR ∞F

& KW

 

 

 

 

 

 

 

 

 

-10

0

10

20

30

40

50

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

MBH

10.876

12.808

15.078

17.744

20.877

24.556

28.879

33.958

 

KW

1.847

1.917

1.987

2.057

2.127

2.198

2.268

2.338

 

 

 

 

 

 

 

 

 

 

 

 

 

750

70

MBH

10.046

11.978

14.248

16.914

20.047

23.726

28.049

33.128

KW

2.135

2.205

2.275

2.345

2.415

2.486

2.556

2.626

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

MBH

9.054

10.986

13.256

15.922

19.055

22.734

27.057

32.136

 

KW

2.377

2.447

2.517

2.587

2.657

2.728

2.798

2.868

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

MBH

11.886

13.818

16.088

18.754

21.887

25.566

29.889

34.968

 

KW

1.731

1.801

1.871

1.941

2.011

2.082

2.152

2.222

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

70

MBH

11.056

12.988

15.258

17.924

21.057

24.736

29.059

34.138

KW

2.019

2.089

2.159

2.229

2.299

2.370

2.440

2.510

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

MBH

10.064

11.996

14.266

16.932

20.065

23.744

28.067

33.146

 

KW

2.261

2.331

2.401

2.471

2.541

2.612

2.682

2.752

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

MBH

13.978

15.910

18.180

20.846

23.979

27.658

31.981

37.060

 

KW

1.881

1.951

2.021

2.091

2.161

2.232

2.302

2.372

 

 

 

 

 

 

 

 

 

 

 

 

 

1250

70

MBH

13.148

15.080

17.350

20.016

23.149

26.828

31.151

36.230

KW

2.169

2.239

2.309

2.379

2.449

2.520

2.590

2.660

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

MBH

12.156

14.088

16.358

19.024

22.157

25.836

30.159

35.238

 

KW

2.411

2.481

2.551

2.621

2.691

2.762

2.832

2.902

 

 

 

 

 

 

 

 

 

 

 

 

 

1.These capacities are net capacities - the indoor motor heat has been added. These power inputs are total power inputs - the indoor motor watts have been added.

Unitary Products Group

11

Page 11
Image 11
York B1HP024 THRU 048 manual HEATING CAPACITIES - 2 TON BHP024, HEATING CAPACITIES - 2-1/2TON BHP030