TABLE 8: HEATING CAPACITIES - 2 TON (BHP024)
CFM | RETURN | CAP1 |
|
| OUTDOOR AIR TEMPERATURE, ∞F (72% RH) |
|
| ||||
AIR ∞F | & KW |
|
|
|
|
|
|
|
| ||
| 0 | 10 | 20 | 30 | 40 | 50 | 60 | ||||
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
| |
| 55 | MBH | 10.216 | 11.748 | 13.601 | 15.843 | 18.554 | 21.834 | 25.801 | 30.601 | |
|
|
|
|
|
|
|
|
|
| ||
| KW | 1.214 | 1.307 | 1.401 | 1.494 | 1.588 | 1.681 | 1.775 | 1.868 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
600 | 70 | MBH | 7.317 | 8.849 | 10.702 | 12.944 | 15.655 | 18.935 | 22.902 | 27.702 | |
|
|
|
|
|
|
|
|
| |||
KW | 1.363 | 1.456 | 1.550 | 1.643 | 1.737 | 1.830 | 1.924 | 2.017 | |||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
| 80 | MBH | 7.205 | 8.737 | 10.590 | 12.832 | 15.543 | 18.823 | 22.790 | 27.590 | |
|
|
|
|
|
|
|
|
|
| ||
| KW | 1.423 | 1.516 | 1.610 | 1.703 | 1.797 | 1.890 | 1.984 | 2.077 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
| 55 | MBH | 10.206 | 11.738 | 13.591 | 15.833 | 18.544 | 21.824 | 25.791 | 30.591 | |
|
|
|
|
|
|
|
|
|
| ||
| KW | 1.227 | 1.320 | 1.414 | 1.507 | 1.601 | 1.694 | 1.788 | 1.881 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
800 | 70 | MBH | 7.307 | 8.839 | 10.692 | 12.934 | 15.645 | 18.925 | 22.892 | 27.692 | |
|
|
|
|
|
|
|
|
| |||
KW | 1.376 | 1.469 | 1.563 | 1.656 | 1.750 | 1.843 | 1.937 | 2.030 | |||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
| 80 | MBH | 7.195 | 8.727 | 10.580 | 12.822 | 15.533 | 18.813 | 22.780 | 27.580 | |
|
|
|
|
|
|
|
|
|
| ||
| KW | 1.436 | 1.529 | 1.623 | 1.716 | 1.810 | 1.903 | 1.997 | 2.090 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
| 55 | MBH | 11.377 | 12.909 | 14.762 | 17.004 | 19.715 | 22.995 | 26.962 | 31.762 | |
|
|
|
|
|
|
|
|
|
| ||
| KW | 1.339 | 1.432 | 1.526 | 1.619 | 1.713 | 1.806 | 1.900 | 1.993 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
1000 | 70 | MBH | 8.478 | 10.010 | 11.863 | 14.105 | 16.816 | 20.096 | 24.063 | 28.863 | |
|
|
|
|
|
|
|
|
| |||
KW | 1.488 | 1.581 | 1.675 | 1.768 | 1.862 | 1.955 | 2.049 | 2.142 | |||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
| 80 | MBH | 8.366 | 9.898 | 11.751 | 13.993 | 16.704 | 19.984 | 23.951 | 28.751 | |
|
|
|
|
|
|
|
|
|
| ||
| KW | 1.548 | 1.641 | 1.735 | 1.828 | 1.922 | 2.015 | 2.109 | 2.202 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
1.These capacities are net capacities - the indoor motor heat has been added. These power inputs are total power inputs - the indoor motor watts have been added.
TABLE 9: HEATING CAPACITIES - 2-1/2 TON (BHP030)
CFM | RETURN | CAP1 |
|
| OUTDOOR AIR TEMPERATURE, ∞F (72% RH) |
|
| ||||
AIR ∞F | & KW |
|
|
|
|
|
|
|
| ||
| 0 | 10 | 20 | 30 | 40 | 50 | 60 | ||||
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
| |
| 55 | MBH | 10.876 | 12.808 | 15.078 | 17.744 | 20.877 | 24.556 | 28.879 | 33.958 | |
| KW | 1.847 | 1.917 | 1.987 | 2.057 | 2.127 | 2.198 | 2.268 | 2.338 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
750 | 70 | MBH | 10.046 | 11.978 | 14.248 | 16.914 | 20.047 | 23.726 | 28.049 | 33.128 | |
KW | 2.135 | 2.205 | 2.275 | 2.345 | 2.415 | 2.486 | 2.556 | 2.626 | |||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
| 80 | MBH | 9.054 | 10.986 | 13.256 | 15.922 | 19.055 | 22.734 | 27.057 | 32.136 | |
| KW | 2.377 | 2.447 | 2.517 | 2.587 | 2.657 | 2.728 | 2.798 | 2.868 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
| 55 | MBH | 11.886 | 13.818 | 16.088 | 18.754 | 21.887 | 25.566 | 29.889 | 34.968 | |
| KW | 1.731 | 1.801 | 1.871 | 1.941 | 2.011 | 2.082 | 2.152 | 2.222 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
1000 | 70 | MBH | 11.056 | 12.988 | 15.258 | 17.924 | 21.057 | 24.736 | 29.059 | 34.138 | |
KW | 2.019 | 2.089 | 2.159 | 2.229 | 2.299 | 2.370 | 2.440 | 2.510 | |||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
| 80 | MBH | 10.064 | 11.996 | 14.266 | 16.932 | 20.065 | 23.744 | 28.067 | 33.146 | |
| KW | 2.261 | 2.331 | 2.401 | 2.471 | 2.541 | 2.612 | 2.682 | 2.752 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
| 55 | MBH | 13.978 | 15.910 | 18.180 | 20.846 | 23.979 | 27.658 | 31.981 | 37.060 | |
| KW | 1.881 | 1.951 | 2.021 | 2.091 | 2.161 | 2.232 | 2.302 | 2.372 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
1250 | 70 | MBH | 13.148 | 15.080 | 17.350 | 20.016 | 23.149 | 26.828 | 31.151 | 36.230 | |
KW | 2.169 | 2.239 | 2.309 | 2.379 | 2.449 | 2.520 | 2.590 | 2.660 | |||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
| 80 | MBH | 12.156 | 14.088 | 16.358 | 19.024 | 22.157 | 25.836 | 30.159 | 35.238 | |
| KW | 2.411 | 2.481 | 2.551 | 2.621 | 2.691 | 2.762 | 2.832 | 2.902 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
1.These capacities are net capacities - the indoor motor heat has been added. These power inputs are total power inputs - the indoor motor watts have been added.
Unitary Products Group | 11 |