TABLE 3: BP072 COOLING CAPACITIES (6 TON) |
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| OUTDOOR AMBIENT TEMPERATURE |
|
|
|
|
|
|
|
| |||||
RETURN AIR |
|
|
| 85°F |
|
|
|
|
|
|
|
| 95°F |
|
|
|
|
| ||||
GROSS | INPUT2 | GROSS SENSIBLE CAPACITY1, MBH | GROSS | INPUT2 | GROSS SENSIBLE CAPACITY1, MBH | |||||||||||||||||
|
| |||||||||||||||||||||
|
| RETURN AIR DRY BULB TEMP. °F | RETURN AIR DRY BULB TEMP. °F | |||||||||||||||||||
|
| CAP.1 | POWER |
|
|
|
|
|
|
|
| CAP.1 | POWER |
|
|
|
|
|
|
|
| |
| WB |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
CFM | TEMP | MBH | kW | 86 | 83 |
| 80 | 77 | 74 | 71 | 68 | MBH | kW | 86 | 83 |
| 80 | 77 | 74 | 71 | 68 | |
| °F |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 72 | 76.1 | 5.26 | 45.5 | 39.7 |
| 33.8 | 28.0 | 22.2 | - | - | 72.6 | 5.80 | 43.1 | 38.0 |
| 32.9 | 27.7 | 22.6 | - | - | |
1800 | 67 | 71.2 | 5.19 | 57.8 | 51.9 |
| 46.1 | 40.3 | 34.4 | 28.6 | 22.8 | 67.0 | 5.74 | 55.0 | 49.9 |
| 44.7 | 39.6 | 34.5 | 29.3 | 24.2 | |
62 | 66.0 | 5.13 | 66.0 | 62.8 |
| 57.0 | 51.2 | 45.3 | 39.5 | 33.7 | 60.9 | 5.67 | 60.9 | 59.8 |
| 54.7 | 49.5 | 44.4 | 39.3 | 34.1 | ||
|
|
| ||||||||||||||||||||
| 57 | 65.4 | 5.12 | 65.4 | 64.0 |
| 58.1 | 52.3 | 46.5 | 40.6 | 34.8 | 60.7 | 5.67 | 60.7 | 59.9 |
| 54.7 | 49.6 | 44.5 | 39.3 | 34.2 | |
| 72 | 78.9 | 5.28 | 49.9 | 43.4 |
| 37.0 | 30.6 | 24.2 | - | - | 75.7 | 5.83 | 48.2 | 42.1 |
| 36.0 | 30.0 | 23.9 | - | - | |
2100 | 67 | 73.8 | 5.21 | 63.3 | 56.9 |
| 50.4 | 44.0 | 37.6 | 31.2 | 24.8 | 69.8 | 5.77 | 61.2 | 55.1 |
| 49.0 | 43.0 | 36.9 | 30.8 | 24.8 | |
62 | 68.3 | 5.15 | 68.3 | 66.8 |
| 62.4 | 56.0 | 49.6 | 43.1 | 36.7 | 63.4 | 5.70 | 63.4 | 62.9 |
| 59.9 | 53.9 | 47.8 | 41.7 | 35.7 | ||
|
|
| ||||||||||||||||||||
| 57 | 67.8 | 5.14 | 67.8 | 67.0 |
| 63.6 | 57.2 | 50.8 | 44.4 | 38.0 | 63.2 | 5.70 | 63.2 | 62.8 |
| 60.0 | 53.9 | 47.9 | 41.8 | 35.7 | |
| 72 | 81.6 | 5.30 | 54.2 | 47.2 |
| 40.2 | 33.2 | 26.2 | - | - | 78.7 | 5.86 | 53.2 | 46.2 |
| 39.2 | 32.2 | 25.2 | - | - | |
2400 | 67 | 76.3 | 5.23 | 68.8 | 61.8 |
| 54.8 | 47.8 | 40.8 | 33.8 | 26.8 | 72.6 | 5.80 | 67.3 | 60.3 |
| 53.3 | 46.3 | 39.4 | 32.4 | 25.4 | |
62 | 70.7 | 5.17 | 70.7 | 70.7 |
| 67.8 | 60.8 | 53.8 | 46.8 | 39.8 | 66.0 | 5.73 | 66.0 | 66.0 |
| 65.2 | 58.2 | 51.2 | 44.2 | 37.2 | ||
|
|
| ||||||||||||||||||||
| 57 | 70.1 | 5.16 | 70.1 | 70.1 |
| 69.1 | 62.1 | 55.1 | 48.1 | 41.1 | 65.7 | 5.72 | 65.7 | 65.7 |
| 65.3 | 58.3 | 51.3 | 44.3 | 37.3 | |
| 72 | 83.3 | 5.31 | 58.0 | 50.1 |
| 42.1 | 34.1 | 26.2 | - | - | 79.6 | 5.87 | 56.9 | 48.9 |
| 41.0 | 33.0 | 25.0 | - | - | |
2700 | 67 | 77.9 | 5.24 | 73.3 | 65.3 |
| 57.4 | 49.4 | 41.4 | 33.5 | 25.5 | 73.4 | 5.81 | 70.8 | 63.7 |
| 55.8 | 47.8 | 39.8 | 31.9 | 23.9 | |
62 | 72.1 | 5.18 | 72.1 | 72.1 |
| 70.7 | 62.7 | 54.7 | 46.8 | 38.8 | 66.7 | 5.74 | 66.7 | 66.7 |
| 66.3 | 58.4 | 50.4 | 42.4 | 34.4 | ||
|
|
| ||||||||||||||||||||
| 57 | 71.6 | 5.17 | 71.6 | 71.6 |
| 71.1 | 63.1 | 55.1 | 47.2 | 39.2 | 66.5 | 5.74 | 66.5 | 66.5 |
| 66.3 | 58.3 | 50.3 | 42.3 | 34.4 | |
| 72 | 84.9 | 5.32 | 61.9 | 52.9 |
| 44.0 | 35.0 | 26.1 | - | - | 80.5 | 5.89 | 60.6 | 51.7 |
| 42.8 | 33.8 | 24.9 | - | - | |
3000 | 67 | 79.5 | 5.25 | 77.8 | 68.9 |
| 59.9 | 51.0 | 42.0 | 33.1 | 24.2 | 74.2 | 5.83 | 74.2 | 67.1 |
| 58.2 | 49.3 | 40.3 | 31.4 | 22.4 | |
62 | 73.6 | 5.19 | 73.6 | 73.6 |
| 73.6 | 64.7 | 55.7 | 46.8 | 37.8 | 67.5 | 5.76 | 67.5 | 67.5 |
| 67.5 | 58.5 | 49.6 | 40.6 | 31.7 | ||
|
|
| ||||||||||||||||||||
| 57 | 73.0 | 5.18 | 73.0 | 73.0 |
| 73.0 | 64.1 | 55.1 | 46.2 | 37.2 | 67.2 | 5.76 | 67.2 | 67.2 |
| 67.2 | 58.3 | 49.4 | 40.4 | 31.5 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| OUTDOOR AMBIENT TEMPERATURE |
|
|
|
|
|
|
|
| |||||
RETURN AIR |
|
|
| 105°F |
|
|
|
|
|
|
|
| 115°F |
|
|
|
|
| ||||
| INPUT2 | GROSS SENSIBLE CAPACITY1, MBH |
| INPUT2 | GROSS SENSIBLE CAPACITY1, MBH | |||||||||||||||||
|
|
|
| |||||||||||||||||||
|
| GROSS | RETURN AIR DRY BULB TEMP. °F | GROSS | RETURN AIR DRY BULB TEMP. °F | |||||||||||||||||
|
| CAP.1 | POWER |
|
|
|
|
|
|
|
| CAP.1 | POWER |
|
|
|
|
|
|
|
| |
| WB |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
CFM | TEMP | MBH | kW | 86 | 83 |
| 80 | 77 | 74 | 71 | 68 | MBH | kW | 86 | 83 |
| 80 | 77 | 74 | 71 | 68 | |
| °F |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 72 | 67.5 | 6.47 | 40.8 | 35.7 |
| 30.6 | 25.5 | 20.3 | - | - | 62.3 | 7.14 | 38.6 | 33.4 |
| 28.3 | 23.2 | 18.0 | - | - | |
1800 | 67 | 61.4 | 6.38 | 52.1 | 46.9 |
| 41.8 | 36.7 | 31.5 | 26.4 | 21.3 | 55.8 | 7.02 | 49.2 | 44.0 |
| 38.9 | 33.8 | 28.6 | 23.5 | 18.4 | |
62 | 56.3 | 6.33 | 56.3 | 55.4 |
| 50.3 | 45.1 | 40.0 | 34.9 | 29.7 | 51.8 | 6.98 | 51.8 | 51.0 |
| 45.9 | 40.7 | 35.6 | 30.5 | 25.3 | ||
|
|
| ||||||||||||||||||||
| 57 | 55.9 | 6.31 | 55.9 | 55.0 |
| 49.9 | 44.8 | 39.6 | 34.5 | 29.4 | 51.1 | 6.95 | 51.1 | 50.2 |
| 45.0 | 39.9 | 34.8 | 29.6 | 24.5 | |
| 72 | 70.8 | 6.51 | 46.1 | 40.1 |
| 34.0 | 27.9 | 21.9 | - | - | 66.0 | 7.19 | 44.1 | 38.0 |
| 32.0 | 25.9 | 19.8 | - | - | |
2100 | 67 | 64.4 | 6.41 | 58.5 | 52.6 |
| 46.5 | 40.4 | 34.4 | 28.3 | 22.2 | 59.1 | 7.06 | 55.7 | 50.0 |
| 43.9 | 37.9 | 31.8 | 25.7 | 19.7 | |
62 | 59.1 | 6.36 | 59.1 | 58.7 |
| 55.9 | 49.8 | 43.7 | 37.7 | 31.6 | 54.8 | 7.03 | 54.8 | 54.4 |
| 51.8 | 45.7 | 39.7 | 33.6 | 27.5 | ||
|
|
| ||||||||||||||||||||
| 57 | 58.6 | 6.34 | 58.6 | 58.2 |
| 55.4 | 49.4 | 43.3 | 37.3 | 31.2 | 54.0 | 6.99 | 54.0 | 53.6 |
| 50.9 | 44.8 | 38.8 | 32.7 | 26.6 | |
| 72 | 74.2 | 6.55 | 51.4 | 44.4 |
| 37.4 | 30.4 | 23.4 | - | - | 69.6 | 7.23 | 49.6 | 42.6 |
| 35.6 | 28.6 | 21.6 | - | - | |
2400 | 67 | 67.4 | 6.45 | 64.8 | 58.2 |
| 51.2 | 44.2 | 37.2 | 30.2 | 23.2 | 62.3 | 7.11 | 62.3 | 56.0 |
| 49.0 | 42.0 | 35.0 | 28.0 | 21.0 | |
62 | 61.9 | 6.40 | 61.9 | 61.9 |
| 61.5 | 54.5 | 47.5 | 40.5 | 33.5 | 57.9 | 7.07 | 57.9 | 57.9 |
| 57.8 | 50.8 | 43.8 | 36.8 | 29.8 | ||
|
|
| ||||||||||||||||||||
| 57 | 61.4 | 6.38 | 61.4 | 61.4 |
| 61.0 | 54.0 | 47.0 | 40.0 | 33.0 | 57.0 | 7.04 | 57.0 | 57.0 |
| 56.7 | 49.7 | 42.7 | 35.7 | 28.7 | |
| 72 | 74.3 | 6.56 | 54.7 | 46.8 |
| 38.8 | 30.8 | 22.8 | - | - | 69.1 | 7.25 | 52.5 | 44.6 |
| 36.6 | 28.6 | 20.7 | - | - | |
2700 | 67 | 67.6 | 6.47 | 66.3 | 61.0 |
| 53.0 | 45.1 | 37.1 | 29.1 | 21.2 | 61.8 | 7.13 | 61.8 | 58.3 |
| 50.3 | 42.3 | 34.4 | 26.4 | 18.4 | |
62 | 62.1 | 6.42 | 62.1 | 62.1 |
| 61.9 | 53.9 | 45.9 | 37.9 | 30.0 | 57.4 | 7.09 | 57.4 | 57.4 |
| 57.4 | 49.4 | 41.4 | 33.5 | 25.5 | ||
|
|
| ||||||||||||||||||||
| 57 | 61.5 | 6.40 | 61.5 | 61.5 |
| 61.3 | 53.4 | 45.4 | 37.4 | 29.5 | 56.6 | 7.06 | 56.6 | 56.6 |
| 56.4 | 48.5 | 40.5 | 32.5 | 24.6 | |
| 72 | 74.5 | 6.58 | 58.0 | 49.1 |
| 40.2 | 31.2 | 22.3 | - | - | 68.6 | 7.27 | 55.4 | 46.5 |
| 37.6 | 28.6 | 19.7 | - | - | |
3000 | 67 | 67.8 | 6.49 | 67.8 | 63.9 |
| 54.9 | 46.0 | 37.0 | 28.1 | 19.1 | 61.4 | 7.15 | 61.4 | 60.6 |
| 51.6 | 42.7 | 33.7 | 24.8 | 15.8 | |
62 | 62.2 | 6.44 | 62.2 | 62.2 |
| 62.2 | 53.3 | 44.3 | 35.4 | 26.5 | 57.0 | 7.11 | 57.0 | 57.0 |
| 57.0 | 48.1 | 39.1 | 30.2 | 21.2 | ||
|
|
| ||||||||||||||||||||
| 57 | 61.7 | 6.42 | 61.7 | 61.7 |
| 61.7 | 52.8 | 43.8 | 34.9 | 25.9 | 56.1 | 7.08 | 56.1 | 56.1 |
| 56.1 | 47.2 | 38.3 | 29.3 | 20.4 |
1.These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 X kW. Refer to the appropriate blower performance table for the KW of the supply air blower motor.
2.These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.
16 | Unitary Products Group |