TABLE 3: BP072 COOLING CAPACITIES (6 TON) - CONTINUED
|
|
| OUTDOOR AMBIENT TEMPERATURE |
|
| ||||||
RETURN AIR |
|
|
| 125°F |
|
|
|
|
| ||
| INPUT2 | GROSS SENSIBLE CAPACITY1, MBH | |||||||||
|
|
| |||||||||
|
| GROSS | RETURN AIR DRY BULB TEMP. °F | ||||||||
|
| CAP.1 | POWER |
|
|
|
|
|
|
|
|
| WB |
|
|
|
|
|
|
|
| ||
CFM | TEMP | MBH | kW | 86 | 83 |
| 80 | 77 | 74 | 71 | 68 |
| °F |
|
|
|
|
|
|
|
|
|
|
| 72 | 57.2 | 7.81 | 36.3 | 31.2 |
| 26.0 | 20.9 | 15.8 | - | - |
1800 | 67 | 50.2 | 7.66 | 46.2 | 41.1 |
| 36.0 | 30.8 | 25.7 | 20.6 | 15.4 |
62 | 47.3 | 7.64 | 47.3 | 46.6 |
| 41.5 | 36.3 | 31.2 | 26.1 | 20.9 | |
|
| ||||||||||
| 57 | 46.2 | 7.59 | 46.2 | 45.3 |
| 40.2 | 35.1 | 29.9 | 24.8 | 19.7 |
| 72 | 61.1 | 7.87 | 42.1 | 36.0 |
| 29.9 | 23.9 | 17.8 | - | - |
2100 | 67 | 53.7 | 7.71 | 53.0 | 47.5 |
| 41.4 | 35.3 | 29.3 | 23.2 | 17.1 |
62 | 50.6 | 7.69 | 50.6 | 50.2 |
| 47.8 | 41.7 | 35.6 | 29.6 | 23.5 | |
|
| ||||||||||
| 57 | 49.5 | 7.64 | 49.5 | 49.0 |
| 46.3 | 40.3 | 34.2 | 28.1 | 22.1 |
| 72 | 65.1 | 7.92 | 47.9 | 40.9 |
| 33.9 | 26.9 | 19.9 | - | - |
2400 | 67 | 57.2 | 7.76 | 57.2 | 53.8 |
| 46.8 | 39.8 | 32.8 | 25.8 | 18.8 |
62 | 53.8 | 7.75 | 53.8 | 53.8 |
| 53.8 | 47.0 | 40.0 | 33.1 | 26.1 | |
|
| ||||||||||
| 57 | 52.7 | 7.70 | 52.7 | 52.7 |
| 52.5 | 45.5 | 38.5 | 31.5 | 24.5 |
| 72 | 63.8 | 7.94 | 50.4 | 42.4 |
| 34.4 | 26.4 | 18.5 | - | - |
2700 | 67 | 56.1 | 7.79 | 56.1 | 55.5 |
| 47.6 | 39.6 | 31.6 | 23.6 | 15.7 |
62 | 52.8 | 7.77 | 52.8 | 52.8 |
| 52.8 | 44.9 | 37.0 | 29.0 | 21.0 | |
|
| ||||||||||
| 57 | 51.6 | 7.72 | 51.6 | 51.6 |
| 51.5 | 43.6 | 35.6 | 27.6 | 19.6 |
| 72 | 62.6 | 7.97 | 52.8 | 43.9 |
| 35.0 | 26.0 | 17.1 | - | - |
3000 | 67 | 54.9 | 7.81 | 54.9 | 54.9 |
| 48.3 | 39.4 | 30.4 | 21.5 | 12.6 |
62 | 51.8 | 7.79 | 51.8 | 51.8 |
| 51.8 | 42.8 | 33.9 | 24.9 | 16.0 | |
|
| ||||||||||
| 57 | 50.6 | 7.74 | 50.6 | 50.6 |
| 50.6 | 41.7 | 32.7 | 23.8 | 14.8 |
1.These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 X kW. Refer to the appropriate blower performance table for the KW of the supply air blower motor.
2.These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.
Unitary Products Group | 17 |