036-21217-001-B-1203

DESCRIPTION

These units are completely assembled, piped, wired, charged and tested at the factory and are shipped ready for immediate installation. Only the power supply wiring, the thermostat wir- ing, the condenser water piping, the condensate drain piping and the ductwork are required to complete the installation.

Units include a one-year limited warranty on all replacement parts and a five-year limited warranty on each compressor.

APPLICATION FLEXIBILITY

These ìcooling onlyî units can be applied with:

1.Cooling towers.

2.Well or surface water providing the temperature and the GPM of the water meet the application limitations of the unit.

3.Brackish or salt water and a secondary heat exchanger. They can be installed:

1.Within the conditioned space as ìfree standingî units without any ductwork. Supply air plenum and return air grille accessories are available for these freestanding applications.

2.In an equipment room with both supply and return air ductwork

GENERAL

Horizontal (CH) units are designed for suspended mounting. HWC models are shipped with ëstraight-throughí evaporator fan discharge as standard. Airflow orientation is field convert- ible to side discharge. Vertical (CU) units are designed for free-standing floor mounting. All units are completely factory wired and pre-piped. Water supply, water outlet, and conden- sate drain connections are via female pipe thread fittings.

All models 5 -25 tons ship as factory-charged unitized pack- ages. The 5 -15 ton units may be field split between the evap- orator /compressor section and the upper blower section; installation is possible through standard height doorways and elevators. All packages are designed for free-standing floor mounting. All models are shipped with vertical evaporator fan discharge as standard. Units are completely factory wired and piped. Dual circuit models feature internally manifolded condensers.

CABINET

All cabinets are completely constructed of 18 Ga. corrosion resistant "Galvalume" coated steel. The entire unit interior (both evaporator and condensing section) is insulated with 1/2" thick, 2 lbs. density insulation. Service panels are equipped with lifting handles for ease of removal and han- dling. Duct flanges for return air intake and evaporator dis-

charge are provided with the unit, for field installation. Duct flange on CU240 evaporator return is incorporated into the fil- ter frame.

REFRIGERATION CIRCUITS

All models utilize "Scroll" type hermetic compressors. Com- pressors are mounted on rubber isolators to minimize vibra- tion transmission. Internal overload protection is provided.

External high pressure and low pressure cutout switches are included in each compressor control circuit. The 5 ton units have a single refrigeration circuit. The 8 -20 ton units feature two independent refrigeration circuits. Each refrigeration cir- cuit includes an adjustable thermal expansion valve (with external equalizer), liquid line filter drier, sight glass/moisture indicator, and service gauge ports.

The evaporator coils are constructed of internally enhanced copper tubes mechanically bonded to rippled aluminum plate fins. The evaporator coil is employed in a draw-through con- figuration, and features inter-laced circuiting. Large evapora- tor coil face area minimizes potential water blow-off.

The high-efficiency tube-in-tube condensers feature a convo- luted inner tube design for optimum performance. Standard models feature a copper inner tube surrounded by a steel outer tube, and carry a 400 psig working pressure rating.

INDOOR FANS

Forward curved, double inlet and double width centrifugal blowers are used for evaporator air movement. Large diame- ter wheels are employed to provide required airflow perfor- mance at minimum rpm and noise levels. Blower wheels are fabricated of galvanized steel. Blowers employ solid steel shafts, supported in permanently lubricated ball bearings. All blowers are belt driven. Variable-pitch motor sheaves allow for field adjustment of blower rpm.

ELECTRICAL/CONTROLS

All units are completely factory wired with all necessary con- trols. Manual reset protection is provided on evaporator blower motors. A manual reset circuit is also provided on each compressor control circuit in the event of high/low pres- sure cutout. A 24 volt control circuit, with oversize trans- former, is provided for field connection. Units are designed to operate with conventional thermostat control interface.

FILTERS

All models are shipped with 2 inch thick medium-efficiency throwaway filters factory installed. Filters are accessible from either front or right side on 5-15 ton models. The CU240 filter rack is external to the cabinet (shipped loose).

Unitary Products Group

3

Page 3
Image 3
York CU060, CH060 manual Description, General

CU060, CH060 specifications

The York CU060 and CH060 units represent a noteworthy combination of efficiency and advanced technological capabilities in the realm of commercial heating and cooling. These models are widely recognized for their robust performance and reliability, making them ideal for a variety of applications.

The CU060 is an air-cooled chiller that excels in providing reliable cooling for medium to large commercial buildings. It employs advanced scroll compressor technology that significantly enhances efficiency during operation. This results in lower energy consumption while maintaining optimal cooling performance. The high-efficiency rating also aligns with environmental regulations, supporting organizations in their sustainability goals.

One of the standout features of the CU060 is its microchannel condenser coils, which facilitate improved heat exchange capabilities. This design not only reduces refrigerant charge but also enhances the overall energy efficiency of the unit. These coils are resistant to corrosion and require less maintenance, contributing to a lower total cost of ownership over time.

On the other hand, the CH060 is designed specifically for heating applications, utilizing a hot water or steam configuration. This unit is ideal for commercial spaces requiring effective climate control during colder months. The CH060 leverages advanced controls and monitoring technologies, allowing users to maintain desired temperature levels with precision. Its ability to integrate seamlessly with building management systems further adds to its appeal, facilitating automated control and real-time monitoring.

Both units are equipped with sound-dampening features to minimize operational noise, making them suitable for installations in noise-sensitive environments such as schools and hospitals. The compact design of the CU060 and CH060 allows for flexible installation options, making them suitable for limited-space applications.

Overall, York's CU060 and CH060 models are notable for their efficiency, innovative engineering, and adaptability to various commercial settings. They stand as reliable choices for organizations seeking to enhance their heating and cooling solutions while minimizing their environmental footprint. With a commitment to performance and sustainability, these units represent a forward-thinking approach to climate control in the commercial sector.