1 of 4
PROJECT:
TAG:
Gross Cooling Capacity [Btuh]: | 150,000* |
Design CFM: | 4,800 |
Energy Efficiency Ratio: | 10.65 EER** |
Net Cooling Capacity [Btuh]: | 144,000** |
Net Cooling CFM: | 4,800 |
|
|
Evaporator Fan No./Type: | 2/CENTRIFUGAL |
Diameter x Width [in]: | 12x9 |
Drive: | Adjustable Belt |
Motor HP : | 2.0 / 3.0 |
[Standard/Oversized] |
|
|
|
Condenser Fan No./Type: | 2/CENTRIFUGAL |
Diameter x Width [in]: | 15x15 |
Drive: | Adjustable Belt |
Motor HP : | 3.0 |
[Standard] |
|
|
|
Evaporator Coil Face Area: | 13.03 [sq ft] |
Rows/FPI : | 3/10 |
Refrigerant Control: | TX Valve |
|
|
Condenser Coil Face Area: | 15.82 [sq ft] |
Rows/FPI: | 4/14 |
|
|
Compressor No./Type: | 2/Scroll |
Refrigerant Circuits: | 2 / Independent |
|
|
Refrigerant: | R22 |
Charge: | 12.13 Lbs./ circuit |
|
|
Filters - Qty./Size: | 2/14x20x2 & 4/14x25x2 |
|
|
Operating Weight [lbs.]: | 1335 |
Shipping Weight [lbs.]: | 1395 |
|
|
Condensate Connection: | 3 / 4 NPT |
|
|
*Cooling performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F wet bulb and CFM listed. Gross capacity does not include the effect of fan motor heat.
**Rated in accordance with ARI Standard
EVAPORATOR FAN PERFORMANCE
MODEL | SUPPLY |
|
|
|
|
|
|
| EXTERNAL STATIC PRESSURE - Inches W.C. |
|
|
|
|
|
| |||||||
0.2 | 0.4 |
| 0.6 | 0.8 | 1.0 | 1.2 | 1.4 | 1.6 | 1.8 | 2.0 | ||||||||||||
# | CFM | RPM | BHP | RPM | BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | RPM | BHP | RPM | BHP | RPM | BHP | ||||||
| 4300 | 717 | 1.06 | 792 | 1.23 | 862 |
| 1.41 | 928 | 1.58 | 989 | 1.75 | 1049 | 1.93 | 1100 | 2.10 | 1165 | 2.30 | 1210 | 2.50 | 1245 | 2.60 |
DPV144 | 4800 | 781 | 1.42 | 850 | 1.62 | 915 |
| 1.81 | 976 | 2.00 | 1035 | 2.20 | 1091 | 2.39 | 1144 | 2.58 | 1197 | 2.79 | 1245 | 2.96 | - | - |
| 5300 | 848 | 1.87 | 912 | 2.08 | 972 |
| 2.29 | 1030 | 2.57 | 1085 | 2.72 | 1138 | 2.94 | 1189 | 3.15 | - | - | - | - | - | - |
NOTE:
1.At high evaporator air flows, and wet bulb conditions, condensate
2.Values include pressure drop from wet coil and clean filters.
3.Shaded areas indicate oversize motors.
CONDENSER FAN PERFORMANCE
|
|
|
| EXTERNAL STATIC | PRESSURE - Inches W.C. |
|
|
|
| |||||
MODEL | OUTDOOR | 0.2 | 0.4 | 0.6 | 0.8 |
| 1.0 | 1.2 | ||||||
# | CFM | RPM | BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | RPM | BHP | |||||
DPV144 | 6600 | 675 | 1.77 | 735 | 2.06 | 792 | 2.46 | 848 | 2.60 | 900 |
| 3.00 | - | - |
ELECTRICAL DATA – STANDARD MOTOR
MODEL | VOLTAGE |
| COMPRESSOR | EVAPORATOR FAN | CONDENSER FAN | MIN. CCT. | MAX FUSE / | ||||
# |
| QTY |
| RLA | LRA | HP | FLA | HP | FLA | AMPACITY | CCT. BKR. AMP |
DPV144 | 2 | @ | 20.7 | 156.0 | 2.00 | 5.9 | 3.00 | 8.7 | 61.18 | 80 | |
DPV144 | 460/3/60 | 2 | @ | 10.0 | 75.0 | 2.00 | 2.8 | 3.00 | 4.0 | 29.30 | 35 |
DPV144 | 575/3/60 | 2 | @ | 8.2 | 54.0 | 2.00 | 2.2 | 3.00 | 3.2 | 23.85 | 30 |
ELECTRICAL DATA – OVERSIZED MOTOR
MODEL | VOLTAGE |
| COMPRESSOR | EVAPORATOR FAN | CONDENSER FAN | MIN. CCT. | MAX FUSE / | ||||
# |
| QTY |
| RLA | LRA | HP | FLA | HP | FLA | AMPACITY | CCT. BKR. AMP |
DPV144 | 2 | @ | 20.7 | 156.0 | 3.00 | 8.7 | 3.00 | 8.7 | 63.98 | 80 | |
DPV144 | 460/3/60 | 2 | @ | 10.0 | 75.0 | 3.00 | 4.0 | 3.00 | 4.0 | 30.50 | 40 |
DPV144 | 575/3/60 | 2 | @ | 8.2 | 54.0 | 3.00 | 3.2 | 3.00 | 3.2 | 24.85 | 30 |
Johnson Controls maintains a continuous product improvement policy, therefore specifications are subject to change without notice.
DESCRIPTION:
DPV144 VERTICAL UNIT AIR-COOLED SELF-CONTAINED
Form YK145.12-PA6 (308)
DATE:
March 2008
Page 10