York D*V DPV240 VERTICAL UNIT, Self-Contained Air-Cooled, Form YK145.12-PA8308, March, 1 of, Date

Models: D*V

1 25
Download 25 pages 33.68 Kb
Page 18
Image 18
DPV240 VERTICAL UNIT

1 of 4

PROJECT:

TAG:

Gross Cooling Capacity [Btuh]:

244,000*

Design CFM:

8,000

Energy Efficiency Ratio:

10.10 EER**

Net Cooling Capacity [Btuh]:

236,000**

Net Cooling CFM:

6,800

 

 

Evaporator Fan No./Type:

2/CENTRIFUGAL

Diameter x Width [in]:

15x15

Drive:

Adjustable Belt

Motor HP :

5.0 / 7.5

[Standard/Oversized]

 

 

 

Condenser Fan No./Type:

2/CENTRIFUGAL

Diameter x Width [in]:

18x13

Drive:

Adjustable Belt

Motor HP :

7.5

[Standard]

 

 

 

Evaporator Coil Face Area:

19.00 [sq ft]

Rows/FPI :

4/10

Refrigerant Control:

TX Valve

 

 

Condenser Coil Face Area:

20.55 [sq ft]

Rows/FPI:

4/14

 

 

Compressor No./Type:

2/Scroll

Refrigerant Circuits:

2 / Independent

 

 

Refrigerant:

R22

Charge:

18.35 Lbs./ circuit

 

 

Filters - Qty./Size:

6/20x25x2

 

 

Operating Weight [lbs.]:

1720

Shipping Weight [lbs.]:

1805

 

 

Condensate Connection:

3 / 4 NPT

 

 

*Cooling performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F wet bulb and CFM listed. Gross capacity does not include the effect of fan motor heat.

**Rated in accordance with ARI Standard 360-2000

EVAPORATOR FAN PERFORMANCE

MODEL

SUPPLY

 

 

 

 

 

 

EXTERNAL STATICPRESSURE - Inches W.C.

 

 

 

 

 

 

0.2

0.4

0.6

 

0.8

 

1.0

1.2

1.4

1.6

1.8

2.0

#

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

7200

657

1.89

717

2.19

774

2.51

829

 

2.84

875

 

3.18

933

3.53

972

3.89

1024

4.26

1072

4.63

1113

5.02

DPV240

8000

717

2.51

772

2.84

825

3.20

875

 

3.55

924

 

3.92

976

4.31

1022

4.72

1062

5.15

1105

5.60

1145

6.07

 

8800

778

3.27

830

3.64

878

4.01

925

 

4.40

970

 

4.79

1015

5.20

1067

5.63

1102

6.08

1140

6.54

1183

7.03

NOTE:

1.At high evaporator air flows, and wet bulb conditions, condensate carry-over may occur. Adjust airflow downward as necessary.

2.Values include pressure drop from wet coil and clean filters.

3.Shaded areas indicate oversize motors.

CONDENSER FAN PERFORMANCE

 

 

 

 

EXTERNAL STATIC

PRESSURE - Inches W.C.

 

 

 

MODEL

OUTDOOR

0.2

0.4

0.6

0.8

1.0

1.2

#

CFM

RPM

BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM

BHP

DPV240

10200

656

3.72

700

4.12

741

4.50

781

4.91

820

5.32

857

5.73

ELECTRICAL DATA – STANDARD MOTOR

MODEL

VOLTAGE

 

COMPRESSOR

EVAPORATOR FAN

CONDENSER FAN

MIN. CCT.

MAX FUSE /

#

 

QTY

 

RLA

LRA

HP

FLA

HP

FLA

AMPACITY

CCT. BKR. AMP

DPV240

208-230/3/60

2

@

33.6

225.0

5.00

13.7

7.50

22.2

111.50

125

DPV240

460/3/60

2

@

17.3

114.0

5.00

6.6

7.50

10.8

56.33

70

DPV240

575/3/60

2

@

13.5

80.0

5.00

5.3

7.50

8.2

43.88

50

ELECTRICAL DATA – OVERSIZED MOTOR

MODEL

VOLTAGE

 

COMPRESSOR

EVAPORATOR FAN

CONDENSER FAN

MIN. CCT.

MAX FUSE /

#

 

QTY

 

RLA

LRA

HP

FLA

HP

FLA

AMPACITY

CCT. BKR. AMP

DPV240

208-230/3/60

2

@

33.6

225.0

7.50

22.2

7.50

22.2

120.00

150

DPV240

460/3/60

2

@

17.3

114.0

7.50

10.8

7.50

10.8

60.53

70

DPV240

575/3/60

2

@

13.5

80.0

7.50

8.4

7.50

8.4

47.18

60

Johnson Controls maintains a continuous product improvement policy, therefore specifications are subject to change without notice.

DESCRIPTION:

DPV240 VERTICAL UNIT

SELF-CONTAINED AIR-COOLED

Form YK145.12-PA8 (308)

DATE:

March 2008