York D3CG, D3CE UNIT DIMENSIONS - D*CE180 & 240 UNITS, CLEARANCES mm / in, Utilities Entry Data

Models: D3CG D3CE

1 20
Download 20 pages 1.89 Kb
Page 15
Image 15
UNIT DIMENSIONS - D*CE180 & 240 UNITS

530.26-TG3YI

UNIT DIMENSIONS - D*CE180 & 240 UNITS

1235 (48-5/8") (180)

1337 (52-5/8") (240)

3181 (125-1/4") (180)

3461 (136-1/4") (240)

616 (24-1/4") (180)

895 (35-1/4") (240)

All dimensions are in millimeters and inches, unless otherwise specified. They are subject to change without notice. Certified dimensions will be provided upon request.

CLEARANCES (mm / in.)

 

 

Front

914 / 36

Back

610 / 24 (Less Economizer)

1245 / 49 (With Economizer)

 

Left Side (Filter Access)

610 / 24 (Less Economizer)

1372 / 54 (With Economizer)

 

Right Side (Outdoor Coil)

914 / 36

Below Unit

0 / 0

 

1829 / 72 With 914 / 36

Above Unit*

Maximum Horizontal Overhang

 

(For Outdoor Air Discharge)

NOTE: Unit and ductwork are approved for zero clearance to combustible materials when equipped with electric heat.

*Units must be installed oudoors. Overhanging structures or shrubs should not obstruct outdoor air discharge outlet.

RETURN AIR

SUPPLY AIR

OUTDOOR AIR (Discharge)

OUTDOOR AIR (Economizer)

UTILITIES ENTRY DATA

 

 

OPENING

 

 

HOLE

 

DIAMETER*

USED FOR

 

 

(mm / in.)

 

 

A

28.6

/ 11¤8 KO

Control

Front

19.1

/ 3¤4 NPS (Fem.)

Wiring

Bottom

 

B

92.1

/ 35¤8 KO

Power

Front

76.2 / 3 NPS (Fem.)

Wiring

Bottom

 

*KO denotes Knockout facility.