UNIT DIMENSIONS - D*CE180 & 240 UNITS
1235
1337
3181
3461
616
895
All dimensions are in millimeters and inches, unless otherwise specified. They are subject to change without notice. Certified dimensions will be provided upon request.
CLEARANCES (mm / in.) | ||
|
| |
Front | 914 / 36 | |
Back | 610 / 24 (Less Economizer) | |
1245 / 49 (With Economizer) | ||
| ||
Left Side (Filter Access) | 610 / 24 (Less Economizer) | |
1372 / 54 (With Economizer) | ||
| ||
Right Side (Outdoor Coil) | 914 / 36 | |
Below Unit | 0 / 0 | |
| 1829 / 72 With 914 / 36 | |
Above Unit* | Maximum Horizontal Overhang | |
| (For Outdoor Air Discharge) |
NOTE: Unit and ductwork are approved for zero clearance to combustible materials when equipped with electric heat.
*Units must be installed oudoors. Overhanging structures or shrubs should not obstruct outdoor air discharge outlet.
RETURN AIR
SUPPLY AIR
OUTDOOR AIR (Discharge)
OUTDOOR AIR (Economizer)
UTILITIES ENTRY DATA
|
| OPENING |
|
| |
HOLE |
| DIAMETER* | USED FOR | ||
|
| (mm / in.) |
|
| |
A | 28.6 | / 11¤8 KO | Control | Front | |
19.1 | / 3¤4 NPS (Fem.) | Wiring | Bottom | ||
| |||||
B | 92.1 | / 35¤8 KO | Power | Front | |
76.2 / 3 NPS (Fem.) | Wiring | Bottom | |||
|
*KO denotes Knockout facility.
Unitary Products Group | 15 |