York DM 048, DM072, DM 060, DM 036 warranty Physical Data, VOLTAGE LIMITATIONS1, 036-21502-002-A-0303

Models: DM 036 DM 048 DM 060 DM072

1 40
Download 40 pages 18.41 Kb
Page 30
Image 30

036-21502-002-A-0303

TABLE 24: PHYSICAL DATA

 

MODELS

 

 

DM

 

 

 

 

 

 

 

 

 

036

048

 

060

072

 

 

 

 

 

 

 

EVAPORATOR

Centrifugal Blower (Dia. x Wd. in.)

12 X 10

12 X 10

 

12 X 10

12 X 11

 

 

 

 

 

 

Fan Motor HP (Direct Drive)

1/2

3/4

 

1

1

BLOWER

 

 

 

 

 

 

 

 

Fan Motor HP (Belt Drive)

1 1/2

1 1/2

 

1 1/2

1 1/2

 

 

 

 

 

 

 

EVAPORATOR

Rows Deep

3

3

 

3

4

 

 

 

 

 

 

Fins Per Inch

13

13

 

13

13

COIL

 

 

 

 

 

 

 

Face Area (Sq. Ft.)

3.6

4.3

 

5.1

5.1

 

 

 

 

 

 

 

 

 

CONDENSER

Propeller Dia. (in.)

24

24

 

24

24

 

 

 

 

 

 

Fan Motor Hp

1/4

1/4

 

1/4

1/4

FANS

 

 

 

 

 

 

 

Nom. CFM

3400

3400

 

3400

3400

 

 

 

 

 

 

 

 

 

CONDENSER

Rows Deep

1

1

 

1

2

 

 

 

 

 

 

Fins Per Inch

16

16

 

22

16

COILS

 

 

 

 

 

 

 

Face Area (Sq. Ft.)

17.1

17.1

 

17.1

16.7

 

 

 

 

 

 

 

 

 

COMPRESSOR

Scroll Type

1

1

 

1

1

(Qty. Per Unit)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR

Quantity Per Unit (15” X 20” X 1” or 2“)

2

2

 

2

2

 

 

 

 

 

 

Quantity Per Unit (14” X 25” X 1” or 2“)

1

1

 

1

1

FILTERS

 

 

 

 

 

 

 

 

Total Face Area (sq. ft.)

6.3

6.3

 

6.3

6.3

 

 

 

 

 

 

 

CHARGE

Refrigerant 22

5/8

6/8

 

6/8

10/0

(lbs./oz.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 25: ELECTRIC HEAT CORRECTION FACTORS

NOMINAL VOLTAGE

VOLTAGE

kW CAP. MULTI-

PLIER

 

 

 

 

 

208

208

1.00

 

 

 

240

230

0.92

 

 

 

480

460

0.92

 

 

 

600

575

0.92

 

 

 

TABLE 26: VOLTAGE LIMITATIONS1

POWER SUPPLY

 

VOLTAGE

 

 

 

 

MIN.

 

MAX.

 

 

 

 

208/230-3-60

187

 

253

 

 

 

 

460-3-60

414

 

506

 

 

 

 

575-3-60

518

 

506

 

 

 

 

1.Utilization Range “A” in accordance with ARI Standard 110.