York DM072, DM 060, DM 048, DM 036 warranty Features, Simplicity, 036-21502-002-A-0303

Models: DM 036 DM 048 DM 060 DM072

1 40
Download 40 pages 18.41 Kb
Page 8
Image 8

FEATURES

All models are available with a wide variety of factory- mounted options such as stainless steel heat exchangers, phase monitor, dirty filter switch, and coil guard to make them suitable for almost every application.

All units are self-contained and assembled on full perimeter base rails with forklift holes on three sides and holes for over- head rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation.

All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizon- tal duct, remove the supply and return air panels on the rear of the unit.

All models are available with these “factory mounted” outdoor air damper options:

Single enthalpy economizer

Motorized outdoor air damper

Supply air blowers are equipped with either a direct drive or a belt drive that can be adjusted to meet the exact require- ments of the job.

All compressors are equipped with internal pressure relief. Every refrigerant circuit includes a liquid line filter-drier, a high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch to protect all system compo- nents.

™ Controls -

™ control boards have

 

Simplicity

Simplicity

 

standardized a number of features previously available

only as options or by utilizing additional controls.

Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0ºF outdoor ambient without additional assis- tance. Optionally, the control board can be pro- grammed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.

Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button.

Fan Delays - Fan on and fan off delays are fully pro- grammable and are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat.

Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the

036-21502-002-A-0303

gas valve, if applicable, and the temperature limit switch on gas heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.

Nuisance Trip Protection- To prevent nuisance trouble calls, the control board uses a “three strikes, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the compressor.

On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.

All units have long lasting powder paint cabinets with 750 hour salt spray test approval under ASTM-B117 procedures.

All models are CSA listed.

Warranty - All models include a one-year limited parts warranty on the complete unit. Compressors and electric heater elements carry a five-year warranty. Gas heat exchangers carry a 10-year parts warranty.

Gas Heat Operation - All gas heat units have a mini- mum AFUE of 80%. Each section includes a durable heat exchanger with aluminized steel or optional stain- less steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards.

The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit.

Electric Heat Operation - All electric heat models are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uni- form distribution of air across the heating elements. Every element is fully protected against excessive tem- perature by thermal limit switches.

The power supply wiring can be routed into the control box through a threaded pipe connection (field supplied) in the base pan of the unit or through a knockout in the wiring panel on the side of the unit.

BAS Controls - York’s Sunline™ series units offer fac- tory mounted BAS controls such as Novar, Honeywell, Johnson, and CPC.

8

Unitary Products Group

Page 8
Image 8
York DM072, DM 060, DM 048, DM 036 warranty Features, Simplicity, 036-21502-002-A-0303