York DM 072 warranty SOUND POWER RATING1, CAPACITY RATINGS - ARI 210/2401, GAS HEAT RATINGS1

Models: DM 072

1 44
Download 44 pages 14.27 Kb
Page 15
Image 15

036-21502-003-A-1105

TABLE 1: SOUND POWER RATING1

 

 

ESP

BLOWER

 

 

 

 

SOUND POWER (db 10-12Watts)

 

 

 

UNIT

CFM

 

 

 

 

 

Octave Band Centerline Frequency (Hz)

 

SWL

dB(A)

SIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

@

 

 

IWG

SPEED

KW

63

125

 

250

500

1,000

2,000

4,000

8,000

dB(A)

 

 

 

10Ft.2

 

 

 

 

036

1,200

0.6

LOW

0.60

84

84

 

74

67

69

62

57

52

74

41

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

048

1,600

0.55

HIGH

0.80

85

85

 

75

68

70

63

58

53

75

42

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

060

2,000

0.45

HIGH

1.00

86

86

 

76

69

71

64

59

54

76

43

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

072

2,200

0.3

HIGH

1.35

87

87

 

77

70

72

65

60

55

77

44

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran- tee requiring a dBA value or sound data in any other form than sound power level ratings.

2.At a distance of 10 feet from the blower.

TABLE 2: CAPACITY RATINGS - (ARI 210/240)1

MODEL

MBH

EER2

SEER3

DM036

36.0

9.1

10.0

DM048

47.4

9.0

10.0

DM060

59.0

9.1

10.0

DM072

72.0

9.0

-

1.80/67°F Indoor and 95°F outdoor.

2.EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt).

3.SEER = Seasonal Energy Efficiency Ratio.

TABLE 3: GAS HEAT RATINGS1

MODEL

MBH

MBH

AFUE

TEMP

INPUT

OUTPUT

(%)

RISE ºF

 

DM036N04

50

40

80.9

15 - 45

DM036N08

100

80

80.5

40 - 70

 

 

 

 

 

DM048N06

75

60

80.9

25 - 55

DM048N10

125

100

80.3

45 - 75

DM060N08

100

80

80.5

25 - 55

DM060N10

125

100

80.3

35 - 65

 

 

 

 

 

DM072N08

100

80

80.5

25 - 55

DM072N10

125

100

80.3

35 - 65

1. All units are single-stage heating.

TABLE 4: 2 STAGE GAS HEAT RATINGS

MODEL1

MBH INPUT

MBH OUTPUT

STEADY STATE EFFICIENCY

RISE

MINIMUM HEATING

1ST STAGE

2ND STAGE

1ST STAGE

2ND STAGE

1ST STAGE

2ND STAGE

MIN.

MAX.

AIRFLOW (CFM)

 

DM036D06

45

75

35.8

60.8

79.4

81.1

35

70

790

DM036D10

69

115

55.2

92

80.0

80.2

55

90

950

DM048D06

45

75

35.7

60.8

79.4

81.1

25

70

790

DM048D10

75

125

60.4

100.6

80.5

80.5

45

75

1230

DM060D06

45

75

35.8

60.8

79.4

81.1

35

70

1010

DM060D10

75

125

60.4

100.6

80.5

80.5

45

75

1230

DM072D06

45

75

35.8

60.8

79.4

81.1

35

70

1230

DM072D10

75

125

60.4

100.6

80.5

80.5

45

75

1230

1. Models are 3Ø only.